7100 Series
Description
Compact Analog Addressable
Fire Alarm Control Panel
The Gamewell-FCI, 7100 Series fire alarm control panel is
a multi processor-based, analog addressable system. The
control panel is a compact, yet expandable, platform.
Intended for commercial, industrial and institutional instal-
lations, the 7100 Series is ideal for life safety and property
protection fire alarm applications.
The basic 7100 Series control panel provides one analog
addressable Signaling Line Circuit (SLC), whether sup-
ports up to 99 analog addressable sensors, as well as sup-
porting up to 98 addressable monitor modules and/or
control points, totaling 197 addresses. The 7100 uses an
advanced protocol that ensures an almost instant
response to events while at the same time suppressing
nuisance alarms.
7100 Series
The system may be programmed with the CAMWorks™
programming utility tool or configured through a compre-
hensive set of intuitive, secure password-protected, front-
panel programming options. This important feature allows
the system to quickly adapt to any future requirements due
to changes in occupancies, building remodels, or other
contingencies.
Features
•
•
•
•
Listed under ANSI/UL® Standard 864 9th Edition.
IBC Seismic Certified.
120 or 240 VAC (optional) input line voltage.
Front panel programming with day/night sensitivity
adjustments.
•
•
80-character alpha-numeric display.
One Style 4 (Class “B”) signaling line circuit. Style 6
(Class “A”) with optional CAOM Module.
Two Style Y (Class “B”) regulated notification appliance
circuits rated for 1.5 amp each. Style Z (Class “A”) with
optional CAOM Module.
The sophisticated circuitry and powerful analog software
enables the 7100 Series fire alarm control panel to read
the specific sensitivity level of each sensor and compen-
sate for changes due to age, dust accumulation or other
environmental factors. The 7100 incorporates the
Gamewell-FCI Listed Integrated Sensitivity Testing (LIST)
which meets NFPA 72 sensitivity testing and maintenance
requirements. The LIST testing allows substantial savings
in both maintenance and service while eliminating nui-
sance alarms.
•
•
FM/UL® Listed for Pre-action/Deluge with optional
MCOM Module.
•
•
•
•
Periodic trouble reminder.
Individual sensor drift compensation.
Dual-stage maintenance alerts (“dirty” and “very dirty”).
Multilevel sensor sensitivity adjustments (front panel
programmable).
The Model 7100-1D features an integral Digital Alarm
Communicator Transmitter (DACT) with all popular trans-
mission formats and a 16-digit telephone number field. It is
8-digit Carrier Information Code (CIC) compliant and also
prevents “dialer-runaway” in the event of intermittent sys-
tem faults. The 7100-1D is UL Listed for Remote Station,
Proprietary, and Central Station fire alarm systems. It
allows ample space for wiring and room for batteries up to
12 A/H capacity.
•
•
Alarm verification per individual sensor.
Positive alarm sequence for sensors or monitor
modules.
continued on the next page
SIGNALING
FM
MEA
APPROVED
Approved
6911-1703:0116 (Non-High Rise) Reference Certificate
3003549 FDNY
S1869
CAMWorks™ is a trademark of Honeywell International, Inc.
Microsoft® Word® is a registered trademark of Microsoft® Corporation.
UL® is a registered trademark of Underwriter’s Laboratories Inc.
COA #s 307-99-E 6911-1703:0118 (High Rise)
of Compliance
7300-1703:0106 (LCD-7100)
VMA-45894-02C
(Revision 1)
307-99-E Vol. II
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2015 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-0466 Rev. N page 1 of 3