Timers
RTE Series — AnalogTimers
Key features:
• 20 time ranges and 10 timing functions
• Time delays up to 600 hours
• Space-saving package
• High repeat accuracy of 0ꢀ2ꢁ
• ON and timing OUT LED indicators
• Standard 8- or 11-pin and 11-blade termination
• 2 form C delayed output contacts
• 10A Contact Rating
Certꢀ Noꢀ E9950913332316 (EMC, RTE)
Certꢀ Noꢀ BL960813332355 (LVD, RTE)
UL Listed
File Noꢀ E66043
General Specifications
Contact Ratings
Operation System
Solid state CMOS Circuit
2 Form C, DPDT
(Delay output)
Contact Configuration
Operation Type
Multi-Mode
Allowable Voltage /
Allowable Current
Time Range
0ꢀ1sec to 600 hours
240V AC, 30V DC / 10A
1800 cycles per hour
Pollution Degree
Over voltage category
2 (IE60664-1)
Maximum Permissible
Operating Frequency
III (IE60664-1)
AF20
AD24
D12
100-240V AC(50/60Hz)
Resistive
10A 240V AC, 30V DC
7A 240V AC, 30V DC
Rated Operational Voltage
Voltage Tolerance
24V AC(50/60Hz)/24V DC
Rated Inductive
12V DC
Load
Horse Power
AF20
AD24
D12
85-264V AC(50/60Hz)
1/6 HP 120V AC, 1/3 HP 240V AC
Rating
20ꢀ4-26ꢀ4V AC(50/60Hz)/21ꢀ6-26ꢀ4V DC
10ꢀ8-13ꢀ2V DC
Electrical
Life
500,000 opꢀ minimum (Resistive)
50,000,000 opꢀ minimum
Mechanical
Input off Voltage
Rated Voltage x10ꢁ minimum
-20 to +65ºC (without freezing)
-30 to +75ºC (without freezing)
35 to 85ꢁRH (without condensation)
80kPa to 110kPa (Operating), 70kPa to 110kPa (Transport)
100msec maximum
Ambient Operating Temperature
Ambient Storage and Transport Temperature
Relative Humidity
Atmospheric Pressure
Reset Time
Repeat Error
0ꢀ2ꢁ, 20msecꢂ
Voltage Error
0ꢀ2ꢁ, 20msecꢂ
Temperature Error
Setting Error
0ꢀ5ꢁ, 20msecꢂ
10ꢁ maximum
Insulation Resistance
100MΩ minimum (500V DC)
Between power and output terminals: 2000V AC, 1 minute
Between contacts of different poles: 2000V AC, 1 minute
Between contacts of the same pole:1000V AC, 1 minute
10 to 55Hz amplitude 0ꢀ5mm2 hours in each of 3 axes
Operating extremes: 98m/sec2 (10G)
Damage limits: 490m/sec2 (50G)
3 times in each of 3 axes
Dielectric Strength
Vibration Resistance
Shock Resistance
Degree of Protection
IP40 (enclosure) (IEC60529)
TYPE
RTE-P1, -B1
120V AC/60Hz 6ꢀ5VA
240V AC/60Hz 11ꢀ6VA
RTE-P2, -B2
6ꢀ6VA
AF20
Power Consumption
(Approx.)
11ꢀ6VA
24V AC 60Hz/DC
D12
3ꢀ4VA/1ꢀ7W
3ꢀ5VA/1ꢀ7W
1ꢀ6W
1ꢀ6W
Mounting Position
Dimensions
Free
RTE-P1, P2
RTE-B1, B2
40Hx 36W x 77ꢀ9D mm
40Hx 36W x 74ꢀ9D mm
ꢂFor the value of the error against a preset
time, whichever the largest, appliesꢀ
RTE-P1
87g
RTE-P2
89g
RTE-B1, -B2
85g
Weight (Approx.)
1705151136