5秒后页面跳转
B224BI PDF预览

B224BI

更新时间: 2024-09-21 06:39:19
品牌 Logo 应用领域
SYSTEMSENSOR /
页数 文件大小 规格书
2页 521K
描述
Low-Profile Intelligent Combination Smoke Detector

B224BI 数据手册

 浏览型号B224BI的Datasheet PDF文件第2页 
INSTALLATION AND MAINTENANCE INSTRUCTIONS  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1-800-SENSOR2, FAX: 630-377-6495  
www.systemsensor.com  
B210LP Plug-in Detector Base  
SPECIfICATIONS  
Diameter:  
Mounting:  
6.1 inches (155 mm)  
4-inch (102 mm) square box with or without plaster ring; Minimum Depth - 1.5 inches (38 mm)  
4-inch Octagon Box; Minimum Depth - 1.5 inches (38 mm)  
31/  
-inch Octagon Box; Minimum Depth - 1.5 inches (38 mm)  
2
Single Gang Box; Minimum Depth - 1.5 inches (38 mm)  
Operating Temperature Range:  
Refer to applicable sensor Operating Temperature Range  
using the Base/Sensor Cross Reference Chart at http:\\www.systemsensor.com  
BEfORE INSTALLINꢀ  
fIꢀURE 1. TERMINAL LAyOUT:  
Please thoroughly read the system wiring and installation manuals, and man-  
ual System Smoke Detectors Application Guide, which provides detailed in-  
formation on detector spacing, placement, zoning, and special applications.  
Copies of these manuals are available from System Sensor or through a Sys-  
tem Sensor distributor.  
TAMPER PROOF  
TAB  
BASE  
TERMINALS  
ꢀENERAL DESCRIPTION  
The B210LP is a plug in detector base intended for use in a 2-wire intelligent sys-  
tem, with screw terminals provided for power (+ and –), and remote annuncia-  
tor connections. Communication takes place over the power (+ and –) lines.  
2
1
3
BASE TERMINALS  
NO.  
FUNCTION  
1
Power (–), Remote Annunciator (–)  
Power (+)  
2
3
Remote Annunciator (+)  
MOUNTINꢀ  
This detector base mounts directly to 31/  
- and 4-inch octagon boxes, 4-inch  
2
C0127-00  
square boxes (with or without plaster rings) and single gang boxes. To mount,  
remove the decorative ring by turning it in either direction to unhook the  
snaps, then separate the ring from the base. Install the base on the box using  
the screws supplied with the junction box and the appropriate mounting slots  
in the base.  
fIꢀURE 2. MOUNTINꢀ DETECTOR TO BOx:  
Place the decorative ring on the base and rotate it in either direction until it  
snaps into place (see Figure 2).  
INSTALLATION WIRINꢀ ꢀUIDELINES  
SNAP ON  
DECORATIVE  
RING  
All wiring must be installed in compliance with all applicable local codes  
and any special requirements of the authority having jurisdiction, using the  
proper wire size. The conductors used to connect smoke detectors to control  
panels and accessory devices should be color-coded to reduce the likelihood  
of wiring errors. Improper connections can prevent a system from responding  
properly in the event of a fire.  
SCREWS  
(NOT SUPPLIED)  
For signal wiring (the wiring between interconnected detectors), it is recom-  
mended that the wire be no smaller than AWG 18. However, the screws and  
clamping plate in the base can accommodate wire sizes up to AWG 12. The  
use of twisted pair wiring or shielded cable for the power (+ and -) loop is  
recommended to minimize the effects of electrical interference.  
If shielded cable is used, the shield connection to and from the detector must  
be continuous by using wire nuts, crimping, or soldering, as appropriate for a  
reliable connection.  
DETECTOR  
BASE  
Make electrical connections by stripping about 3/  
inch (10 mm) of insulation  
8
from the end of the wire (use strip gauge molded in base), sliding the bare end  
of the wire under the clamping plate, and tightening the clamping plate screw.  
Do not loop the wire under the clamping plate.  
BOX  
(NOT SUPPLIED)  
The zone wiring of the detector base should be checked before the detector  
heads are installed in them. The wiring should be checked for continuity and  
polarity in the base, and dielectric tests should be performed.  
The base includes a label for recording the zone, address, and type of detector  
being installed. This information is important to set the address of the detector  
head that will later be plugged into the base and to verify the type required  
for that location.  
C0128-00  
D250-01-00  
1
I56-0595-007R  

与B224BI相关器件

型号 品牌 获取价格 描述 数据表
B224RB SYSTEMSENSOR

获取价格

Intelligent Low Profile Plug-in Detectors
B224RB GAMEWELL-FCI

获取价格

Low Profile Analog Laser Sensor
B-225-14X MOLEX

获取价格

Ring Terminal
B-225-56X MOLEX

获取价格

Ring Terminal
B-227 TE

获取价格

B-227 3PDT, Center Off, 60 Amps, 115/200 VAC, 400 Hz
B-228-06HDX MOLEX

获取价格

Ring Terminal, 2.5mm2,
B-228-06HDXT MOLEX

获取价格

Ring Terminal, 3mm2,
B-228-08HDX MOLEX

获取价格

InsulKrimp™ Ring Tongue Terminal for 14-16 He
B-228-08HDXT MOLEX

获取价格

InsulKrimp? Ring Tongue Terminal for 14-16 AWG
B-228-10HDX MOLEX

获取价格

InsulKrimp? Ring Tongue Terminal for 14-16 Heavy Duty AWG Wire