DN-6923:A1 • H-352
XP 1 0 -M
Te n -In p u t Mo n it o r Mo d u le
Ad d re s s a b le De vic e s
Ge n e ra l
The XP10-M ten-input monitor module provides an interface
between a control panel and normally open contact devices in
intelligent alarm systems such as pull stations, security con-
tacts, or flow switches.
The first address on the XP10-M is set from 01 to 150 and the
remaining modules are automatically assigned to the next nine
higher addresses. Provisions are included for disabling a maxi-
mum of two unused addresses.
The supervised state (normal, open, or short) of the monitored
device is sent back to the panel. A common SLC input is used
for all modules, and the initiating device loops share a common
supervisory supply and ground — otherwise each monitor oper-
ates independently from the others.
Each XP10-M module has panel-controlled green LED indica-
tors. The panel can cause the LEDs to blink, latch on, or latch off.
Fe a t u re s
6923xp10.jpg
•
Ten addressable Class B or five addressable Class A initiat-
ing device circuits.
•
Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²)
plug-in terminal blocks.
Maximum IDC wiring res is tance: 1500 ohms.
•
•
•
•
•
•
•
Status indicators for each point.
Maximum IDC voltage: 12 VDC.
Maximum IDC current: 1 mA.
Unused addresses may be disabled.
Rotary address switches.
Class A or Class B operation.
Ag e n c y Lis t in g s a n d Ap p ro va ls
FlashScan® or CLIP operation.
Mount one or two modules in a BB-XP cabinet (optional).
The listings and approvals below apply to the XP10-M Ten-Input
Monitor Module. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may be
in process. Consult factory for latest listing status.
Mount up to six modules on a CHS-6 chassis in a CAB-3
Series, CAB-4 Series, EQ Cabinet Series, or BB-25 cabinet
(optional).
•
•
•
•
•
•
UL Listed: file S3705.
•
Mounting hardware included.
ULC Listed: file S635 (XP10-MA).
CSFM approved: file 7300-0028:219.
FM approved.
S p e c ific a t io n s
Standby current: 3.5 mA (SLC current draw with all addresses
used; if some addresses are disabled, the standby current
decreases).
MEA approved: file 43-02-E.
Maryland State Fire Mars hal approved: Permit #2106.
Alarm current: 55 mA (assumes all ten LEDs solid ON).
P ro d u c t Lin e In fo rm a t io n
XP10-M: Ten-input monitor module.
Temperature range: 32°F to 120°F (0°C to 49°C) for UL appli-
cations; –10°C to +55°C for EN54 applications.
Humidity: 10% to 85% noncondensing for UL applications; 10%
to 93% noncondensing for EN54 applications.
XP10-MA: Same as above with ULC Listing.
BB-XP: Optional cabinet for one or two modules. Dimensions,
DOOR: 9.234" (23.454 cm) wide (9.484" [24.089 cm] including
hinges), x 12.218" (31.0337 cm) high, x 0.672" (1.7068 cm)
deep; BACKBOX: 9.0" (22.860 cm) wide (9.25" [23.495 cm]
including hinges), x 12.0" (30.480 cm) high x 2.75" (6.985 cm);
CHASSIS (installed): 7.150" (18.161 cm) wide overall x 7.312"
(18.5725 cm) high interior overall x 2.156" (5.4762 cm) deep
overall.
Dimens ions : 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x
1.25" (31.75 mm) deep.
Shipping weight: 1.1 lb. (0.499 kg) including packaging.
Mounting options : CHS-6 chassis, BB-25 cabinet, BB-XP cab-
inet, CAB-3 Series cabinet (see DN-3549), CAB-4 Series cabi-
net (see DN-6857), or EQ Cabinet Series (see DN-60229).
Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²).
BB-25: Optional cabinet for up to six modules mounted on
CHS-6 chassis (below). Dimensions, DOOR: 24.0" (60.96 cm)
wide x 12.632" (32.0852 cm) high, x 1.25" (3.175 cm) deep,
hinged at bottom; BACKBOX: 24.0" (60.96 cm) wide x 12.550"
(31.877 cm) high x 5.218" (13.2537 cm) deep.
Power-limited circuits must employ type FPL, FPLR, or FPLP
cable as required by Article 760 of the NEC.
XP10-M is s hipped in Clas s B pos ition; remove shunt for
Class A operation.
Maximum SLC wiring res is tance: 40 or 50 ohms, panel
dependent.
CHS-6: Chassis, mounts up to six modules in a CAB-3 Series
(see DN-3549), CAB-4 Series (see DN-6857) cabinet, EQ Cabi-
net Series (see DN-60229), or BB-25.
DN-6923:A1 • 8/3/07 — Page 1 of 2