描述
6 3 6 - 7 4 5 WAT T S B AT T E R Y C H A R G E R S Y S T E M

PB314 数据手册

 浏览型号PB314的Datasheet PDF文件第2页浏览型号PB314的Datasheet PDF文件第3页 
PB314 Series  
6 3 6 - 7 4 5 W AT T S B AT T E R Y C H A R G E R S Y S T E M  
FEATURES  
636 - 745W  
PSU for Battery Backup  
DC UPS Connectable  
Constant Float Voltage & Current Limit  
Circuit Breaker & Alarm Relays  
Optional LVD - Low Volts Battery Disconnect  
OPERATIONS & INSTALLATION HANDBOOK AVAILABLE  
SPECIFICATIONS  
INPUT  
DISPLAYS AND ALARMS  
DC OK  
LED Green On = OK, Voltage-free changeover  
contact (32V, 1A).Alarm on failure of AC/DC PSU  
and tripping of over temperature limit.  
Input Voltage  
Frequency:  
85-264Vac or 120-360Vdc  
47 to 63 Hz  
Input Current:  
Inrush current:  
Line regulation  
OUTPUT  
4.1A typical at 200Vac  
40A typical cold start 200Vac  
60mV maximum  
LED Green On = OK, Voltage-free changeover  
contact (32V, 1A). Alarm on mains fail.  
AC OK  
LED Green On = OK, Voltage-free changeover  
contact(32V, 1A). Alarm on battery low voltage or  
on opening of battery circuit breaker.  
Battery Ok  
Output Voltage  
Output Power  
Output Current  
Efficiency  
13.8Vdc, 27.6Vdc  
636W - 745W  
See Selection Table  
79% typical  
Battery low alarm voltage -11.0Vdc  
Option LVD:  
Battery LVD disconnect 10.5V  
Battery LVD reconnect 12.0Vdc  
Battery Low Voltage  
Disconnect  
Load regulation  
Ripple  
1% typical  
Voltage meter  
0 to 15Vdc  
160mVp-p max  
180mVp-p max  
Load current meter  
Battery current meter  
OPTIONAL FEATURES  
0 to 100A  
Noise  
-100A to +100A scale.  
PROTECTION  
Overvoltage shutdown  
Output short circuit  
16.2 to 19.8V latching  
Option BCL: Specify battery charge current based  
on battery size.  
Battery Charge Limit  
Indefinite protection (Autoresetting)  
Battery charger short circuit Indefinite protection (Autoresetting)  
Option LVD: For 12V and 24V models, not  
available in 48V models.  
Battery LVD disconnect  
Load output protection  
Thermal - Magnetic Circuit Breaker  
Thermal - Magnetic Circuit Breaker.  
Battery output protection  
STANDARDS & APPROVALS  
C-Tick  
Input - Output: 3KVac 1 min  
Input - Ground: 2KVac 1 min  
Output - Ground: 500Vac 1min  
AS/NZS CISPR11 Group 1 Class A.  
UL 60950 Class 1  
Isolation  
Safety  
EMC  
Emissions comply with AS/NZ CISPR22 Class-B  
ENVIRONMENT  
MECHANICAL  
AC input socket  
-20°C to 71°C  
Derating from 50°C to 71°C to 50% power  
Operating temperature  
IEC320 fused / on off switch  
Hirose connector (-H version)  
Cage clamp terminals (-C version)  
Humidity  
Cooling  
20-90% relative humidity (non condensing)  
Forced cooling - internal fan  
Output termination  
Alarm relay contacts  
DB25 socket  
63 A  
Load fault current  
proteciton breaker  
Battery fault current  
protection breaker  
Rack mount size  
Weight  
63 A  
264 L x 172 W x 67 H mm  
5.0Kg  
Doc. No. PB314 Series Rev.J 29-9-15  

与PB314相关器件

型号 品牌 获取价格 描述 数据表
PB314005 TE

获取价格

Miniature Power PCB Relay PB
PB314006 TE

获取价格

Miniature Power PCB Relay PB
PB314012 TE

获取价格

Miniature Power PCB Relay PB
PB314024 TE

获取价格

Miniature Power PCB Relay PB
PB314-12-43-C POWERBOX

获取价格

6 3 6 - 7 4 5 WAT T S B AT T E R Y C H A R G E R S Y S T E M
PB314-12-43-H POWERBOX

获取价格

6 3 6 - 7 4 5 WAT T S B AT T E R Y C H A R G E R S Y S T E M
PB314-12-53-C POWERBOX

获取价格

6 3 6 - 7 4 5 WAT T S B AT T E R Y C H A R G E R S Y S T E M
PB314-24-27-C POWERBOX

获取价格

6 3 6 - 7 4 5 WAT T S B AT T E R Y C H A R G E R S Y S T E M
PB314-24-27-C-LVD POWERBOX

获取价格

6 3 6 - 7 4 5 WAT T S B AT T E R Y C H A R G E R S Y S T E M
PB314-24-27-H POWERBOX

获取价格

6 3 6 - 7 4 5 WAT T S B AT T E R Y C H A R G E R S Y S T E M