PB314 Series
6 3 6 - 7 4 5 W AT T S B AT T E R Y C H A R G E R S Y S T E M
FEATURES
•
•
•
•
•
•
•
636 - 745W
PSU for Battery Backup
DC UPS Connectable
Constant Float Voltage & Current Limit
Circuit Breaker & Alarm Relays
Optional LVD - Low Volts Battery Disconnect
OPERATIONS & INSTALLATION HANDBOOK AVAILABLE
SPECIFICATIONS
INPUT
DISPLAYS AND ALARMS
DC OK
LED Green On = OK, Voltage-free changeover
contact (32V, 1A).Alarm on failure of AC/DC PSU
and tripping of over temperature limit.
Input Voltage
Frequency:
85-264Vac or 120-360Vdc
47 to 63 Hz
Input Current:
Inrush current:
Line regulation
OUTPUT
4.1A typical at 200Vac
40A typical cold start 200Vac
60mV maximum
LED Green On = OK, Voltage-free changeover
contact (32V, 1A). Alarm on mains fail.
AC OK
LED Green On = OK, Voltage-free changeover
contact(32V, 1A). Alarm on battery low voltage or
on opening of battery circuit breaker.
Battery Ok
Output Voltage
Output Power
Output Current
Efficiency
13.8Vdc, 27.6Vdc
636W - 745W
See Selection Table
79% typical
Battery low alarm voltage -11.0Vdc
Option LVD:
Battery LVD disconnect 10.5V
Battery LVD reconnect 12.0Vdc
Battery Low Voltage
Disconnect
Load regulation
Ripple
1% typical
Voltage meter
0 to 15Vdc
160mVp-p max
180mVp-p max
Load current meter
Battery current meter
OPTIONAL FEATURES
0 to 100A
Noise
-100A to +100A scale.
PROTECTION
Overvoltage shutdown
Output short circuit
16.2 to 19.8V latching
Option BCL: Specify battery charge current based
on battery size.
Battery Charge Limit
Indefinite protection (Autoresetting)
Battery charger short circuit Indefinite protection (Autoresetting)
Option LVD: For 12V and 24V models, not
available in 48V models.
Battery LVD disconnect
Load output protection
Thermal - Magnetic Circuit Breaker
Thermal - Magnetic Circuit Breaker.
Battery output protection
STANDARDS & APPROVALS
C-Tick
Input - Output: 3KVac 1 min
Input - Ground: 2KVac 1 min
Output - Ground: 500Vac 1min
AS/NZS CISPR11 Group 1 Class A.
UL 60950 Class 1
Isolation
Safety
EMC
Emissions comply with AS/NZ CISPR22 Class-B
ENVIRONMENT
MECHANICAL
AC input socket
-20°C to 71°C
Derating from 50°C to 71°C to 50% power
Operating temperature
IEC320 fused / on off switch
Hirose connector (-H version)
Cage clamp terminals (-C version)
Humidity
Cooling
20-90% relative humidity (non condensing)
Forced cooling - internal fan
Output termination
Alarm relay contacts
DB25 socket
63 A
Load fault current
proteciton breaker
Battery fault current
protection breaker
Rack mount size
Weight
63 A
264 L x 172 W x 67 H mm
5.0Kg
Doc. No. PB314 Series Rev.J 29-9-15