Current Transducer LA 25-NP
IPN = 5-6-8-12-25 A
For the electronic measurement of currents : DC, AC, pulsed,
mixed, with a galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronic circuit).
16080
Electrical data
IPN
IP
RM
Primary nominal r.m.s. current
Primary current, measuring range
Measuring resistance @
25
0 .. ± 36
TA = 70°C
RM min RMmax RM min RMmax
At
At
Features
TA = 85°C
· Closed loop (compensated) multi-
range current transducer using the
Hall effect
· Insulated plastic case recognized
according to UL 94-V0.
with ± 15 V
@ ± 25 At max
@ ± 36 At max
100 320 100 315
100 190 100 185
W
W
ISN
KN
VC
IC
Vd
Vb
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
25
mA
1-2-3-4-5 : 1000
± 15
10 + IS
2.5
600
1700
Advantages
V
Current consumption
mA
kV
V
· Excellent accuracy
· Very good linearity
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
R.m.s. rated voltage 1), safe separation
basic isolation
· Low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
V
Accuracy - Dynamic performance data
X
Typical accuracy @ IPN , TA = 25°C
Linearity error
± 0.5
< 0.2
%
%
e
L
· Current overload capability.
Typ Max
± 0.05 ± 0.15 mA
IO
IOM
IOT
Offset current2) @ IP = 0, TA = 25°C
Residual current 3) @ IP = 0, after an overload of 3 x IPN ± 0.05 ± 0.15 mA
Thermal drift of IO
Applications
0°C .. + 25°C
+ 25°C .. + 70°C
- 25°C .. + 85°C
- 40°C .. + 85°C
± 0.06 ± 0.25 mA
± 0.10 ± 0.35 mA
· AC variable speed drives and servo
motor drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies
(UPS)
· Switched Mode Power Supplies
(SMPS)
· Power supplies for welding
applications.
± 0.5
± 1.2
mA
mA
tr
Response time 4) @ 90 % of IPN
< 1
> 50
DC .. 150
µs
A/µs
kHz
di/dt di/dt accurately followed
f
Frequency bandwidth (- 1 dB)
General data
TA
TS
RP
RS
Ambient operating temperature
Ambient storage temperature
Primary resistance per turn
Secondary coil resistance
- 40 .. + 85
- 45 .. + 90
< 1.25
110
°C
°C
mW
W
@ TA = 25°C
@ TA = 70°C
@ TA = 85°C
115
W
RIS
m
Isolation resistance @ 500 V, TA = 25°C
Mass
> 1500
22
MW
g
Standards
EN 50178 : 1997
1)
Notes : Pollution class 2
2)
Measurement carried out after 15 mn functioning
The result of the coercive field of the magnetic circuit
With a di/dt of 100 A/µs.
3)
4)
060327/13
Page 1/2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
www.lem.com