Power Entry Modules with Line Filter
GRF4
www.schurter.com/pg06
IEC Appliance Inlet C14 with Filter, "Lock and Shield" Mounting
Standard- or Medical-Filter
GRF4: with shield and line filter
C14
70° C
Description
Characteristics
-ꢀPanelꢀMount:
-ꢀTimeꢀsavingꢀ"LockꢀandꢀShield"ꢀsnap-inꢀdesignꢀforꢀrear-panelꢀmounting
-ꢀAllꢀsingleꢀelementsꢀareꢀalreadyꢀwired
ꢀ Snap-inꢀversionꢀfromꢀrear-sideꢀ
-ꢀ3ꢀFunctions:
ꢀ ApplianceꢀInletꢀProtectionꢀclassꢀI,ꢀwithꢀEMC-shield,ꢀLineꢀfilterꢀinꢀstan-
dardꢀandꢀmedicalꢀversionꢀ
-ꢀInnovativeꢀEMC-shieldingꢀwithꢀflexibleꢀsteelꢀsegmentsꢀforꢀanꢀexcellentꢀ
contactꢀtoꢀtheꢀpanel
-ꢀQualifiedꢀforꢀuseꢀinꢀequipmentꢀaccordingꢀIEC/ENꢀ60950
-ꢀAlternative:ꢀversionꢀwithoutꢀlineꢀfilterꢀꢀGRF2ꢀ
Other versions on request
-ꢀPanelꢀthicknessꢀ1.2ꢀmmꢀandꢀ2.0ꢀmm
Approvals
-ꢀVDEꢀLicenseꢀNumber:ꢀ102348
-ꢀULꢀLicenseꢀNumber:ꢀE72928
-ꢀCSAꢀLicenseꢀNumber:ꢀ701867
References
GeneralꢀProductꢀInformation
Weblinks
Approvals,ꢀRoHS,ꢀCHINA-RoHS,ꢀMatingꢀConnectors,ꢀe-Store,ꢀ
Distributor-Stock-Check,ꢀAccessories
Technical Data
RatingsꢀIEC
RatingsꢀUL/CSA
LeakageꢀCurrent
0.5ꢀ-ꢀ10ꢀAꢀ@ꢀTaꢀ40ꢀ°Cꢀ/ꢀ250ꢀVAC;ꢀ50ꢀHz
0.5ꢀ-ꢀ15ꢀAꢀ@ꢀTaꢀ40ꢀ°Cꢀ/ꢀ125ꢀVAC;ꢀ60ꢀHz
standardꢀ<ꢀ0.5ꢀmAꢀ(250ꢀVꢀ/ꢀ60ꢀHz)ꢀ
medicalꢀ<ꢀ5ꢀµAꢀ(250ꢀVꢀ/ꢀ60ꢀHz)
>ꢀ1.7ꢀkVDCꢀbetweenꢀL-Nꢀ
>ꢀ2.7ꢀkVDCꢀbetweenꢀL/N-PEꢀ
Testꢀvoltageꢀ(2ꢀsec)
-25ꢀ°Cꢀtoꢀ85ꢀ°C
25/085/21ꢀacc.ꢀtoꢀIECꢀ60068-1
fromꢀfrontꢀsideꢀIPꢀ40ꢀacc.ꢀtoꢀIECꢀ60529
Suitableꢀforꢀappliancesꢀwithꢀprotectionꢀ
classꢀ1ꢀacc.ꢀtoꢀIECꢀ61140
Appliance-Inlet/-Outlet
LineꢀFilter
C14ꢀacc.ꢀtoꢀIEC/ENꢀ60320-1,ꢀ
ULꢀ498,ꢀCSAꢀC22.2ꢀno.ꢀ42ꢀ(forꢀcoldꢀ
conditions)ꢀpin-temperatureꢀ70ꢀ°C,ꢀ10ꢀA,ꢀ
ProtectionꢀClassꢀ1
StandardꢀandꢀMedicalꢀVersion,ꢀIECꢀ
60939,ꢀIECꢀ60601-1,ꢀULꢀ1283,ꢀULꢀ544,ꢀ
ENꢀ133ꢀ200,ꢀCSAꢀC22.2ꢀno.ꢀ8ꢀ
Technicalꢀdetails
DielectricꢀStrength
AllowableꢀOperationꢀTemp.
ClimaticꢀCategory
DegreeꢀofꢀProtection
ProtectionꢀClass
MTBF
>ꢀ3'300'000ꢀhꢀacc.ꢀtoꢀMIL-HB-217ꢀF
Terminal
PanelꢀThicknessꢀs
Quickꢀconnectꢀterminalsꢀ4.8ꢀxꢀ0.8ꢀmm
Snap-in:ꢀ1.5ꢀmmꢀ
(otherꢀonꢀrequest)
Material:ꢀHousing
Thermoplastic,ꢀblack,ꢀULꢀ94V-0
Dimensions
GRF4
30.25
24.3
4.8+0.2 24.2
0.ꢁ
M4
6.ꢀꢁ
4.8x0.8
1)
ꢀ)
max. Rꢀ.5
0.ꢀ
30.5
31.4
0.ꢀ
S
1) Terminal for earth screw M4
This area must be conductive for optimal
shielding. Do not apply paint or coatings.
EMC Products
ꢀ