Relays
New Series GD
6A, 230/240VAC, 300VDC
SINGLE THROW FOUR POLE
Series GD
Force guided relay rated for 6A, 230/240 Vac, 300 Vdc Available
in 4 pole configuration. Polarized DC Drive. See Table 1 for part
numbers.
ELECTRICAL SPECIFICATIONS
GENERAL SPECIFICATIONS
Parameter
Min Typ Max Units
FEATURES:
Operate Time (See Note 1)
Release Time (See Note 1)
Switching Frequency
Shock (11 msec, See Note 3)
Vibration (10-200 Hz, See Note 3)
Electrical Life
17
7
msec
msec
Hz
• Force Guided Contacts per EN50205:
Consists of at least one NO and one NC
contact mechanically linked. This allows
the contact‘s behavior to be pre-
determined and the user the ability to
monitor the contact.The mechanism
provides true status.
5
10
5
g
g
• Dielectric designed for 3-phase systems.
105
107
-25
Cycles
Cycles
oC
• Contacts are physically linked making it
impossible for a NO and NC to be closed
simultaneously.
Mechanical Life
Ambient Temperature
80
• Internal creepage distances and
clearances are designed for Overvoltage
Category III and Degree of Pollution 2 per
IEC 60664.
CONTACT SPECIFICATIONS
Maximum Load Current
• Wide range of Contact configurations and
Coil Voltages.
1 Contacts
2 Contacts
6
A
A
A
4.2
3.5
APPROVALS:
3 Contacts
CUL: Approved
TÜV / VDE: Pending
Maximum Switching Voltage
230/240 Vac
300 Vdc
Maximum Load Capacity (Resistive)
Maximum Switching Capacity
(Inductive)
1500/30 VA/W
ACCESSORIES:Contact Factory
AC15-230/240V
DC13-24V
4
2
Arms
Adc
Current regulator unit DIL housing
Current regulator unit SO.8 housing
Removing tool
Socket with soldering pins for PCB mounting
Socket for conventional mounting.
Contact Resistance (See Note 2)
Dielectric Test Voltage (O=III, P=2)
Coil to Contact
100 mOhm
2500 Vac
2000 Vac
Contact to Contact
© 2000 TELEDYNE RELAYS
800-284-7007 • www.teledynerelays.com
GD 1