DRA3R Series
• Three Phase Motor Reversing Contactor
• Ratings of 2.4 & 4.2 Amps
• Load voltage range of 48-510VAC, 3-Phase
• Fits standard 35mm DIN-RAIL
• LED input status indicator, Forward (green), Reverse (yellow)
• AC or DC control
• cUL Recognized, IEC Rated, CE & RoHS Compliant, Horsepower Rated
• Built in Overvoltage Protection
PRODUCT SELECTION
Description
2.4A
4.2A
4-6 VDC Control
DRA3R48D2
DRA3R48E2
DRA3R48C2
DRA3R48B2
DRA3R48A2
DRA3R48D4
DRA3R48E4
DRA3R48C4
DRA3R48B4
DRA3R48A4
18-28 VDC Control
36-60 VAC Control
90-140 VAC Control
200-265 VAC Control
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS AC Output (1)
Description
2.4 A
48-510
1600
4.2 A
48-510
1600
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk]
Maximum Resistive Load Current (UL508,AC51) [Arms] (2)
Maximum Motor Load Current (UL508,AC53) [Arms] (2)
Minimum Load Current [Arms]
2.4
2.1
0.15
4.2/3.5
3.4
0.15
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (3)
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk]
Maximum I²t for Fusing (50/60 HZ, 1/2 cycle) [A² sec]
HP/IEC 60947 Rating @ 240V, 40°C [HP/KW]
HP/IEC 60947 Rating @ 380V, 40°C [HP/KW]
HP/IEC 60947 Rating @ 480V, 40°C [HP/KW]
Minimum Power Factor (with Maximum Load)
Min/Max stranded/solid wire [AWG]
3.0
500
2.6
285/300
410/375
1/2 / 0.37
1.0 / 0.75
1.0 / 0.75
0.5
3.0
500
2.6
285/300
410/375
1.0 / 0.75
1.5 / 1.1
2.0 / 1.5
0.5
24/10
24/10
Min/Max stranded/solid wire [AWG]
24/10
24/10
Load Terminal Screw Torque Range:
12.0 in lb (1.36 Nm)
12.0 in lb (1.36 Nm)