Power Entry Modules with Line Filter
CD
https://www.schurter.com /PG06
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole (5x20 mm or 6.3x32 mm), Line Switch 1- or
2-pole, Voltage Selector (Step)
C14
See below:
Approvals and Compliances
70° C
Description
Characteristics
- All single elements are already wired
- The fuse drawer "Fingergrip" can be removed by hand
- Panel mount :
Screw-on mounting front side
- For applications according IEC/UL 62368-1 we recommend variants
with bleed resistor
Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
- 5 Functions :
Appliance Inlet , Line Switch , Fuseholder with interchangeable fuse
drawer for Fuse-links 5x20 mm or 6.3x32 mm , with or without voltage
selector (step switch) , Line filter in standard and medical version
- V-Lock notch standard
References
Alternative: version without line filter KD
- Quick connect terminals 4.8 x 0.8 mm
Unique Selling Proposition
- Multifunctional Power Entry Module
- Solid metal flange
- Various fuse drawers
- Slim design
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
1 - 10A @ Ta 40 °C / 250VAC; 50Hz
1 - 10A @ Ta 40 °C / 250VAC; 60Hz
standard < 0.5mA (250V / 60Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7kVDC between L-N
> 2.7kVDC between L/N-PE
Test voltage (2sec)
-25°C to 85°C
Appliance inlet/-outlet
Fuseholder
C14 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10A,
Protection Class I
1-/2-pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 / 6.3 x 32mm
5 x 20: 2.5W (1 pole)/ 2W (2-pole) per
pole
6.3 x 32: 3.15W (1 pole)/ 2.5W (2-pole)
per pole
Admissible power acceptance at higher
ambient temperature see derating cur-
ves
2-pole, non-illuminated, acc. to IEC
61058-1
Technical Details
optional, step, 2-4 digits
Dielectric Strength
Rated Power Acceptance @
Ta 23 °C
Allowable Operation Tempe-
rature
Climatic Category
IP-Protection
25/085/21 acc. to IEC 60068-1
front side IP40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Screw: max 8mm
Power Acceptance @ Ta >
23°C
Protection Class
Terminal
Panel Thickness S
Line Switch
Mounting screw torque max 0.5Nm
Thermoplastic, black, UL 94V-0
Material
Voltage Selector
Line Filter
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
MTBF
> 1'200'000h acc. to MIL-HB-217 F
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.
1
EMC Products