Flex Series
GWF402 and
GWF404
2 and 4 Zone Conventional
Fire Alarm Control Panels
Description
The Flex 402 is a two zone fire alarm control panel (FACP)
and the Flex 404 is a four zone FACP. These control pan-
els provide reliable fire signaling protection for small to
medium sized retail, office, multi-family, or other similar
c om me r ci al o r i n st i tu t i on al bu il d in g .
Initiating device circuits (IDCs) for Flex Series panels are
power limited and operate in Style B (Class B). Each panel
is compatible with conventional input devices such as two-
wire smoke detectors, four-wire smoke detectors, pull sta-
tions, water flow devices, tamper switches and other nor-
mally-open contact devices. This includes System Sensor
GWF402 (left) and GWF404 (right)
i3™ Series microprocessor-based detectors with advanced
features like drift compensation, maintenance alert and
freeze warning. (See Device Compatibility Document PN
52195 for a listing of compatible devices.)
Features
•
Flex 402: Two Style B (Class B) IDC zones, one Style Y
(Class B) NAC
Outputs include one notification appliance circuit (NAC) on
the Flex 402 and two NACs on the Flex 404. NACs are
power limited and operate in Style Y (Class B). Each FACP
has a Form-C Alarm and Trouble relay and 24 VDC special
applications resettable power. In addition, the Flex 404 has
a Form-C Supervisory relay and a special application non-
resettable power output. The FACP supervises wiring, AC
voltage and battery level.
•
Flex 404: Four Style B (Class B) IDC zones, two Style Y
(Class B) NACs
•
•
Optional NAC Class A converter module (Flex 404)
NAC synchronization and programmability features:
- ADA compliant strobe synchronization
- ANSI audible signals as required by NFPA 72
- Silence inhibit, auto-silence, non-silenceable
- Selective Silence: mute horns, keep strobes lit
- Temporal or steady signal
Silent or audible walk test from front keypad
Zone disable, alarm verification selectable per zone
Controls: Acknowledge, Alarm, Silence, Reset,
Walktest, Zone enable/disable
LED indicators: Alarm, Supervisory, Maintenance,
Trouble (one per zone): AC, NAC / Zone disable, NAC
fault, System / Power Trouble, Walktest, Alarm Silence,
Charger / Battery / Earth Fault (on pcb)
Alarm verification
Activation of a compatible smoke detector or any normally-
open fire alarm initiating device will activate audible and
visual signaling devices, illuminate an indicating LED,
sound the piezo sounder at the FACP, activate the FACP
alarm relay and operate and optional modules used to
notify a remote station or initiate an auxiliary control
function.
•
•
•
•
Both the Flex 402 and Flex 404 fire alarm control panels
®
are listed to UL Standard 864, 9th Edition.
•
•
•
Low AC voltage sense, automatic battery charger
Piezo sounder for alarm, trouble, and supervisory
An ISO 9000-2000 Company
SIGNALING
i 3™ is a trademark of Honeywell International Inc.
MEA
UL® is a registered trademark of Underwriter’s Laboratories Inc.
Approved
S521 366-04-E 7165-1288:180
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
©2007 by Honeywell International Inc. All rights reserved.
Specifications are for information only, are not intended for installation pwurpwoswes,.ganadmareeswubejecllt-tofcchia.cngoemwithout notice. No responsibility is assumed by Gamewell-FCI for their use.
9021-60292 Rev. A page 1 of 2