80W Constant Power Mode LED Driver
SLD-80 series
SPECIFICATION
MODEL
SLD-80-56
RATED CURRENT
RATED POWER
1400mA
Note.2 78.4W
CONSTANT CURRENT REGION Note.3 30 ~56V
FULL POWER CURRENT RANGE 1400~2100mA
OPEN CIRCUIT VOLTAGE (max.) 60V
OUTPUT
CURRENT ADJ. RANGE
CURRENT RIPPLE
CURRENT TOLERANCE
700~2100mA
5.0%(@rated current)
±5%
SET UP TIME
Note.5
500ms/230VAC, 1200ms/115VAC
110 ~ 305VAC
155VDC ~ 431VDC
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
Note.2
(Please refer to "STATIC CHARACTERISTIC" and “ DRIVING METHODS OF LED MODULE"section)
47 ~ 63Hz
PF≧0.97 / 115VAC, PF≧0.95 / 230VAC, PF≧0.92 / 277VAC at full load
(Please refer to "Power Factor Characteristic" section)
THD< 10% (@ load≧60% at 115VAC/230VAC ,@load≧75% at 277VAC)
Please refer to “TOTAL HARMONIC DISTORTION (THD)” section
TOTAL HARMONIC DISTORTION
INPUT
EFFICIENCY (Typ.)
92.0%
AC CURRENT (Typ.)
INRUSH CURRENT(Typ.)
0.9A / 115VAC
0.45A / 230VAC
0.38A / 277VAC
COLD START 50A(twidth=270μs measured at 50% Ipeak) at 230VAC; Per NEMA 410
8 unit(circuit breaker of type B) / 16 units(circuit breaker of type C) at 230VAC
<0.25mA / 277VAC
MAX. NO. of PSUs on 16A
CIRCUIT BREAKER
LEAKAGE CURRENT
NO LOAD POWER CONSUMPTION <0.5W
110 ~ 150%
OVER POWER
Hiccup mode, recovers automatically after fault condition is removed
Hiccup mode, recovers automatically after fault condition is removed
60 ~ 70V
Shut down output voltage, re-power on to recovery
Hiccup mode, recovers automatically after fault condition is removed
Tcase=-20 ~ +90℃(Please refer to "OUTPUT LOAD vs TEMPERATURE" section)
Tcase=+90℃
20 ~ 95% RH non-condensing
-40 ~ +80℃
SHORT CIRCUIT
OVER VOLTAGE
PROTECTION
ENVIRONMENT
OVER TEMPERATURE
WORKING TEMP.
MAX. CASE TEMP.
WORKING HUMIDITY
STORAGE TEMP.
TEMP. COEFFICIENT
VIBRATION
±0.03%/℃ (0 ~ 60℃)
10 ~ 500Hz, 2G 12min./1cycle, period for 72min. each along X, Y, Z axes
UL8750(type”HL”),CSA C22.2 No. 250.13-12, ENEC EN61347-1, EN61347-2-13 independent, EN62384,
EAC TP TC 004, GB19510.1,GB19510.14
SAFETY STANDARDS Note.4
WITHSTAND VOLTAGE
I/P-O/P:3.75KVAC
ISOLATION RESISTANCE
I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION
Note.4 Parameter
Standard
Test Level/Note
EN55015(CISPR15) ,GB/T17743
EN55015(CISPR15) ,GB/T17743
EN61000-3-2 ,GB/T17625.1
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN61547
-----
-----
Class C @load≥60%
-----
SAFETY &
EMC
EN61000-3-3
EMC IMMUNITY
Parameter
ESD
Radiated
Standard
EN61000-4-2
EN61000-4-3
Test Level/Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 2
EFT/Burst
Surge
Conducted
Magnetic Field
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
Level 2
1KV/Line-Line
Level 2
Level 2
>95% dip 0.5 periods, 30% dip 25 periods,
Voltage Dips and Interruptions
EN61000-4-11
>95% interruptions 250 periods
MTBF
867.33K hrs min. Telcordia SR-332 (Bellcore) ;
320*30*16.8mm (L*W*H)
0.206 Kg; 64pcs / 14.184Kg / 0.75CUFT
260.96K hrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION
PACKING
NOTE
℃
℃
℃℃
File Name:SLD-80-SPEC 2019-09-16