Protection Relays and Controls
Ground-Fault Protection–Grounded Systems
SE-701 SERIES (PGR-5701)
Ground-Fault Monitor
Description
The SE-701 is a microprocessor-based ground-fault relay for resistance-
and solidly-grounded systems. In addition to common systems, it is
uniquely suited for use on systems with significant harmonic content.
The SE-701 can provide main-plant protection, feeder-level protection,
or individual-load protection. Proper current transformer selection
provides the desired pickup range.The output contacts can be
connected for use in protective tripping circuits or in alarm indication
circuits.The analog output can be used with a PLC or a meter.
Features & Benefits
FEATURES
BENEFITS
Adjustable pickup
(1-99%)
Trip setting based on input CT primary, allows use with
any CT. Minimum 50 mA with EFCT Series.
Adjustable time delay
(50 ms-2.5 s)
Adjustable trip delay allows quick protection and system
coordination
Form A and Form B ground-fault output contacts for
operation of separate annunciation and trip circuits
Output contacts
Analog output
(0-5V)
Allows for connecting an optional meter (PGA-0500) or a
control system
Simplified Circuit Diagram
CT-Loop monitoring
Alarms when CT is not connected
Compatible with variable-speed drives
Eliminates nuisance tripping
Selectable DFT or peak
detection filtering
A
Cꢆ
A
Harmonic filtering
Non-volatile trip
memory
Retains trip state while de-energized to simplify
troubleshooting
GROꢃꢄDED
SꢃPPLꢅ
ꢀ
C
Microprocessor based
No calibration required, saves on maintenance cost
Allows operation in application where one side of PT is
faulted, provides flexibility for numerous applications
Universal power supply
Accessories
Ground-Fault CurrentTransformer
A
Required current transformer model depends on
application. We offer a variety of sensitive CTs with
5- and 30-A primaries.
SE-701 SERIES
ꢀꢁrounꢂꢃꢄault ꢅonitorꢆ
Lꢂ
Lꢁ
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter displays
ground-fault current as a percentage of the CT
primary rating.
Ordering Information
ORDERING NUMBER
SE-701-OU
Specifications
IEEE Device Numbers
Input Voltage
Ground fault (50G/N, 51G/N)
See ordering information
H 75 mm (3.0"); W 55 mm (2.2"); D 115 mm (4.5")
1-99% CT-Primary Rating
0.05-2.5 s
CONTROL POWER
120/240 Vac/Vdc
12/24 Vdc
Dimensions
Trip Level Settings
Trip Time Settings
SE-701-OD
Contact Operating Mode Selectable fail-safe or non-fail-safe
SE-701-OT
48 Vdc
Harmonic Filtering
Test Button
Standard feature
Standard feature
SE-701-O3
24 Vac
Reset Button
Standard feature
Standard feature
Isolated Form A and Form B
CSA certified, UL Listed (E340889),
CE (European Union), C-Tick (Australian)
0-5 V
Consult factory
5 years
DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)
ACCESSORIES
REQUIREMENT
Required
CT-Loop Monitoring
Output Contacts
Approvals
Current Transformer
PGA-0500
Optional
Analog Output
Conformally coated
Warranty
PMA-55, PMA-60
SE-EFVC Voltage Clamp
Optional
Optional
Mounting
Note: For optional conformal coating please consult factory.