Protection Relays and Controls
Ground-Fault Protection–Grounded Systems
SE-703 SERIES
Earth-Leakage Monitor
Description
The SE-703 is a microprocessor-based earth-fault relay for resistance-
and solidly earthed systems. It offers sensitive earth-fault detection as
low as 25 mA and can be used on systems with significant harmonic
content.The SE-703 provides feeder-level protection or individual-load
protection.The output contacts can be connected for use in protective
tripping circuits or in alarm indication circuits.The analog output can be
used with a PLC or a meter.The SE-703 is specifically designed to be
AS/NZS 2081 compliant to either 2011 or 2002 (see ordering options).
Features & Benefits
FEATURES
BENEFITS
Adjustable pickup
(25-500 mA)
Adjustable trip setting provides a wide range of low-
level protection and system coordination
Adjustable time delay Adjustable trip delay allows quick protection and
(INST-500 ms)
system coordination
2 Form C ground-fault output contacts for operation of
separate annunciation and trip circuits
Output contacts
Analog output
(0-5V)
Allows for connecting an optional meter (PGA-0500)
or control system
Simplified Circuit Diagram
ꢀꢁ
CT-Loop monitoring
Alarms when CT is not connected
A
Contact operating
mode
Fail-safe operating mode for undervoltage
ꢍ
ꢎ
ꢀ
ꢄꢅꢆꢇꢈꢉEꢉ
ꢊꢇꢋꢋLꢌ
applications, optional non-fail-safe mode available
Harmonic filtering
Eliminates nuisance tripping
Non-volatile trip
memory
Retains trip state while de-energized to simplify
troubleshooting
Microprocessor based No calibration required, saves maintenance cost
Universal
power supply
Allows operation in application where one side of PT is
faulted, provides flexibility for numerous applications
Compliant with US, Canadian, European, and Australian
standards for applications in almost any country
SE-703 SERIES
(Earth-Leakage Monitor)
Global certifications
Lꢃ
Lꢂ
Accessories
A
EFCT Series Ground-Fault CurrentTransformer
Required zero-sequence current transformer
specifically designed for low-level detection.
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter displays ground-
fault current as a percentage of the set-point or 5 A.
Ordering Information
ORDERING NUMBER
SE-703-0U-0x
CONTROL POWER
120/240 Vac/Vdc
12/24 Vdc
PMA-60 Series – Mounting Adapter
Required when panel mounting for
AS/NZS 2081:2011 compliance
SE-703-0D-0x
Specifications
SE-703-0T-0x
48 Vdc
IEEE Device Numbers
Input Voltage
Ground fault (50G/N, 51G/N)
See ordering information
H 75 mm (3.0"); W 55 mm (2.2"); D 115 mm (4.5")
25-500 mA
SE-703-03-0x
24 Vac
Dimensions
Trip Level Settings
Trip Time Settings
Note: x=0 for AS/NZS 2081:2011 compliance (fail-safe output contacts)
x=2 for AS/NZS 2081:2002 compliance (selectable fail-safe or non-fail-safe
output contacts
INST-500 ms
Contact Operating Mode Fail-safe (x=0 models) or selectable (x=2 models)
Harmonic Filtering
Test Button
Reset Button
CT-Loop Monitoring
Output Contacts
Approvals
Standard feature
Standard feature
ACCESSORIES
EFCT Series
PGA-0500
REQUIREMENT
Required
Optional
Standard feature
Standard feature
Two isolated Form C contacts
CSA certified, UL Listed (E340889),
CE (European Union), RCM (Australian)
AS/NZS 2081:2011 (x=0 models) or
AS/NZS 2081: 2002 (x=2 models)
0-5 V
PMA-55
Optional
Compliance
PMA-60
Optional
SE-EFVC Voltage Clamp
Optional
Analog Output
Conformally coated
Warranty
Yes
5 years
Mounting
DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)
Rev: 4-D-091517
Based on Manual Rev 12-B-092117
© 2017 Littelfuse Protection Relays & Controls
Littelfuse.com/se-703