Protection Relays and Controls
Ground-Fault Protection–Grounded Systems
SE-703 SERIES
Earth-Leakage Monitor
Description
The SE-703 is a microprocessor-based earth-fault relay for resistance-
and solidly earthed systems. It offers sensitive earth-fault detection as
low as 25 mA and can be used on systems with significant harmonic
content.The SE-703 provides feeder-level protection or individual-load
protection.The output contacts can be connected for use in protective
tripping circuits or in alarm indication circuits.The analog output can be
used with a PLC or a meter.The SE-703 is specifically designed to be
AS/NZS 2081 compliant to either 2011 or 2002 (see ordering options).
Features & Benefits
FEATURES
BENEFITS
Adjustable pickup
(25-500 mA)
Adjustable trip setting provides a wide range of low-level
protection and system coordination
Adjustable time delay
(INST-500 ms)
Adjustable trip delay allows quick protection and
system coordination
Form A and Form B or 2 Form C ground-fault output
contacts for operation of separate annunciation and
trip circuits
Allows for connecting an optional meter (PGA-0500) or
control system
Output contacts
Simplified Circuit Diagram
Analog output
(0-5V)
ꢀꢁ
A
CT-Loop monitoring
Alarms when CT is not connected
ꢍ
ꢎ
ꢀ
ꢄꢅꢆꢇꢈꢉEꢉ
ꢊꢇꢋꢋLꢌ
Contact operating
mode
Fail-safe operating mode for undervoltage applications,
optional non-fail-safe mode available
Harmonic filtering
Eliminates nuisance tripping
Non-volatile trip
memory
Retains trip state while de-energized to simplify
troubleshooting
Microprocessor based No calibration required, saves maintenance cost
Universal
power supply
Allows operation in application where one side of PT is
faulted, provides flexibility for numerous applications
SE-703 SERIES
(Earth-Leakage Monitor)
(Output contacts
vary by model)
Lꢃ
Lꢂ
Accessories
EFCT Series Ground-Fault CurrentTransformer
Required zero-sequence current transformer
specifically designed for low-level detection.
A
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter displays ground-
fault current as a percentage of the set-point or 5 A.
Ordering Information
ORDERING NUMBER
SE-703-OU
PMA-60 Series – Mounting Adapter
Required when panel mounting for AS/NZS 2081:2011
compliance
CONTROL POWER
120/240 Vac/Vdc
12/24 Vdc
48 Vdc
SE-703-OD
Specifications
SE-703-OT
IEEE Device Numbers
Input Voltage
Ground fault (50G/N, 51G/N)
See ordering information
H 75 mm (3.0"); W 55 mm (2.2"); D 115 mm (4.5")
25-500 mA
SE-703-03
SE-703-xx-001
SE-703-xx-021,2
24 Vac
Dimensions
As above
Trip Level Settings
Trip Time Settings
Contact Operating Mode Fail-safe unless noted
Harmonic Filtering
Test Button
INST-500 ms
As above
Standard feature
ACCESSORIES
EFCT Series
PGA-0500
REQUIREMENT
Required
Optional
Standard feature
Reset Button
Standard feature
CT-Loop Monitoring
Output Contacts
Approvals
Standard feature
Isolated Form A and Form B unless noted
CSA certified, UL Listed (E340889),
CE (European Union), RCM (Australian) unless noted
AS/NZS 2081:2011 unless noted
0-5 V
PMA-55
Optional
PMA-60
Optional
Compliance
Analog Output
Conformally coated
Warranty
SE-EFVC Voltage Clamp
Optional
Yes
5 years
NOTES:
1
2
Two Form C contacts. CSA and UL certification pending.
Selectable fail-safe/non-fail-safe operating modes (AS/NZS 2081:2002 compliant)
Mounting
DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)
Rev: 4-C-032917
Based on Manual Rev 12-A-031017
© 2017 Littelfuse Protection Relays & Controls