Solid State Relays
Industrial, 1-Phase Analog Switching
Type RM1E
• AC Solid State Relay
• Analog switching (phase-angle control) for resistive
and slightly inductive load applications
• 4 - 20mA or 0 -10V control input
• Rated operational current: 25, 50 and 100 AACrms
• Rated operational voltage: Up to 600 VACrms
• Variable intensity LED-indication according to input
current
• Integral snubber network
RM1E..AA
RM1E..V
Product Description
Ordering Key
RM 1E 60 AA 50
The analog switching relay zero output power whilst 20 mA
works in accordance with the or 10VDC correspond to full
phase angle control principle, output power (near linear pow-
i.e., the output switching point er response). The relay switch-
in the AC sine wave depends es off every time the output
on the control input which can current crosses zero, and
be either 4-20mA or 0-10VDC. switches ON in accordance
4 mA or 0VDC correspond to with the applied control input.
Solid State Relay
Number of Poles
Switching mode
Rated operational voltage
Control input
Rated operational current
Type Selection
Switching mode
Rated operational
voltage
Rated operational
current
Control input
E: Analog switching
23: 230 VACrms*
40: 400 VACrms
48: 480 VACrms
60: 600 VACrms
25: 25 AACrms
50: 50 AACrms
100: 100 AACrms
AA: 4 - 20 mADC
V:
0-10VDC**
* For nominal operational voltage of 110VACrms, use RM1E23...
** RM1E..V.. require an external supply voltage
Selection Guide
Rated operational Blocking voltage Control input
voltage
Rated operational current
25 A
50 A
100 A
230 VAC
650 Vp
4 - 20 mA
0-10 VDC
4 - 20 mA
4 - 20 mA
0-10 VDC
4 - 20 mA
0-10 VDC
RM1E23AA25
RM1E23V25
RM1E40AA25
RM1E48AA25
RM1E48V25
RM1E60AA25
RM1E60V25
RM1E23AA50
RM1E23V50
RM1E40AA50
RM1E48AA50
RM1E48V50
RM1E60AA50
RM1E60V50
RM1E23AA100
RM1E23V100
RM1E40AA100
RM1E48AA100
RM1E48V100
RM1E60AA100
RM1E60V100
400 VAC
480 VAC
850 Vp
1200 Vp
600 VAC
1400 Vp
General Specifications
RM 1E 23 ...
RM 1E 40 ...
RM 1E 48 ...
RM 1E 60 ...
Operational voltage range
RM1E..AA..
90 to 280 VAC
90 to 265 VAC
340 to 460 VAC
-
90 to 550 VAC
200 to 550 VAC
410 to 660 VAC
410 to 660 VAC
RM1E..V..
Blocking voltage
Operational frequency range
Power factor
650 Vp
45 to 65 Hz
> 0.75
850 Vp
45 to 65 Hz
> 0.75
1200 Vp
45 to 65 Hz
> 0.75
1400 Vp
45 to 65 Hz
> 0.75
Approvals
CE-marking
* Approvals pending for RM1E..V...
UL, cUL, CSA*
Yes
UL, cUL, CSA*
Yes
UL, cUL, CSA*
Yes
UL, cUL, CSA*
Yes**
** Heatsink must be connected to ground for 600V types
1