MODEL: R7G
Remote I/O R7 Series
GATEWAY MODULE
FUNCTIONS & FEATURES
The Gateway Module for CC-Link and HLS (Hi-speedLink
System) connects discrete I/O between the networks each
other. The module hands over 32 point inputs of CC-Link to
32 point outputs of HLS or 32 point inputs of HLS to 32 point
outputs of CC-Link.
CAUTION
In this module, the transmission between CC-Link and HLS is
not synchronized. Therefore, if one of the networks read
the transmitted data before completion of its update by the
other network, the data may be uncertain as 16-bit data. If
the correct 16-bit data is necessary, arrange the host
application program.
MODEL: R7G-SC-S[1]-R[2]
Refer to the instruction manual.
ORDERING INFORMATION
• Code number: R7G-SC-S[1]-R[2]
Specify a code from below for each [1] and [2].
(e.g. R7G-SC-SHL-R/Q)
GENERAL SPECIFICATIONS
Connection
• Specify the specification for option code /Q
(e.g. /C01)
• Power supply, CC-Link: Screwless spring terminal
Applicable wire size: 0.2 - 1.25 mm
2
Stripped length: 10 mm
Module type of network 1
S: Slave
Recommended solderless terminal
AI0,25-10YE 0.25 mm
AI0,34-10TQ 0.34 mm
AI0,5-10WH 0.5 mm
AI0,75-10GY 0.75 mm
A1-10 1.0 mm (Phoenix Contact)
A1,5-10 1.5 mm (Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
Type of network 1
C: CC-Link
2
(Phoenix Contact)
(Phoenix Contact)
2
2
2
Module type of network 2
• HLS: RJ-45 Connectors
S: Slave
Recommended cable connector:
TM21P-88P (Hirose Electric)
[1] Type of network 2
HL: HLS (Hi-speedLink System) Full-duplex
(not included in the package)
Isolation: CC-Link or FG to HLS to power
Station address setting: Rotary switch
(For the detail refer to the instruction manual.)
Transfer rate
HL1: HLS (Hi-speedLink System) Half-duplex
POWER INPUT
DC Power
• CC-Link Rotary switch
R: 24 V DC
• HLS DIP switch
(For the detail refer to the instruction manual.)
Power LED: Green LED turns on when the power is supplied.
Status indicator LED
[2] OPTIONS
blank: none
• CC-Link: Red LEDs indicate communication status.
• HLS: Green LEDs indicate communication status.
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
COMMUNICATION
■ HLS COMMUNICATION
Network: Full-duplex or half-duplex
Transmission distance:
/C02: Polyurethane coating
/C03: Rubber coating
• 12 Mbps: 100 meters (328 ft)
• 6 Mbps: 200 meters (656 ft)
R7G SPECIFICATIONS
ES-7817 Rev.3 Page 1/6
http://www.m-system.co.jp/