MODEL: R3-PA8
Remote I/O R3 Series
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
TOTALIZED PULSE INPUT MODULE
(Pi 8 points, 32 Bits)
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
27.5 [1.08]
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8457)
130
[5.12]
RELATED PRODUCTS
• Interface module (model: R3-NC1, R3-NC3, R3-NE1,
R3-NMx, R3-NDx, R3-NFL1, R3-NP1, R3-NFx, R3-NML3.
R3-NF2: Firmware version V0.05 or later)
109
[4.29]
Note:
mm [inch]
• Count reset by host PC/PLC:
Available with this unit and the above mentioned interface
modules of firmware version V2.00 or later, except R3-NFx
(R3-NM3: Firmware version V1.00 or later). Notice that
Count reset by host PC/PLC via R3-NFx or interface module
of previous versions of firmware is unable.
MODEL: R3-PA8[1][2]
ORDERING INFORMATION
• Code number: R3-PA8[1][2]
• Count preset by host PC/PLC:
It is only available in combination with this unit displayed
'SW3-4 RESET/PRESET' on the right side panel and the
interface module R3-NMx or R3-NE1 of firmware version
V2.00 or later. Count preset is not available for other
combination (R3-NM3: Firmware version V1.00 or later).
Notice that this function is not available in the same time as
count preset by host PC/PLC.
Specify a code from below for each of [1] and [2].
(e.g. R3-PA8W/A/CE/PRS/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
8: 8
• In the FL-net Configuration Builder software (model: R3-
NFLBLD), the number of channel for this module is
displayed as 16 because data has 8 channels x 2 words.
[1] COMMUNICATION MODE
S: Single
W: Dual
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base
(model: R3-BSx)
[2] OPTIONS (multiple selections)
Excitation
Blank: Internal (negative common)
/A: External (24 V DC, negative common)
Standards & Approvals
Screw terminal: Nickel-plated steel
Isolation: Input to internal bus or internal power
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with excitation abnormality;
blank: Without CE
/CE: CE marking
EX-FACTORY SETTING
blank: Enable count reset by host PC/PLC
/PRS: Enable count preset by host PC/PLC
Other Options
blank: none
Green in normal operating conditions.
Input status indicator: Red LED;
/Q: Option other than the above (specify the specification)
1 to 8: Turns on with the input ON.
9 to 15: Unused
16: Turns on with the reset input ON.
R3-PA8 SPECIFICATIONS
ES-8457 Rev.10 Page 1/5
https://www.m-system.co.jp/