MODEL: R3-PD16
Remote I/O R3 Series
RELATED PRODUCTS
• Interface module (model: R3-Nx)
Output completion status is compatible with interface
modules model: R3-NC1, -NC3, -NE1, -NM1 and -NDx of
firmware version V2.00 or higher. Other interface modules
are not compatible. So, set I/O Mode as output (SW2-7: ON)
to use it.
ONE-SHOT PULSE OUTPUT MODULE
(relay contact output, 16 points)
27.5 [1.08]
Note: R3-NL1 and R3-NL2 are not available with this model.
GENERAL SPECIFICATIONS
Connection
130
[5.12]
Internal bus: Via the Installation Base (model: R3-BSx)
Output: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
109
[4.29]
mm [inch]
Isolation: Output to internal bus or internal power
Output mode setting: One-Shot Output Mode, ON/OFF
Control Output Mode, Continuance Output Mode selectable
with DIP switch
MODEL: R3-PD16[1][2]
Output data length: 16bit, 8bit selectable with DIP switch
(For ON/OFF Control Output Mode only)
I/O mode setting: Output Complete Status ON/OFF is
selectable with DIP switch
ORDERING INFORMATION
• Code number: R3-PD16[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-PD16W/CE/Q)
One-shot ON time setting: 0.1 to 25.6 sec. selectable with
DIP switch
• Specify the specification for option code /Q
(e.g. /C01/SET)
ON/OFF control output setting: Swappable its pair with DIP
switch.
Output hold function: Setting for communication error with
side DIP SW (available in continuance output mode)
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/ green) LED;
Green in normal operating conditions;
Red with abnormal configuration.
NO. OF CHANNELS
16: 16
[1] COMMUNICATION MODE
S: Single
W: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
Output status indicator: Red LED; turns on with the output
ON.
/CE: CE marking
Other Options
OUTPUT SPECIFICATIONS
Output: Relay contact, 16 points
blank: none
/Q: Option other than the above (specify the specification)
Common: All 16 points (4 terminals)
Common current: Max. 4 A (total of 4 terminals)
Rated load: 250 V AC @ 0.5A (cos ø = 1)
(Less than 50 V AC to conform with EU Directive.)
30 V DC @ 0.5 A (resistive load)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
electrical life 10 cycles (6 cycles/min.)
5
/C03: Rubber coating
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 30 W
Minimum load: 1 V DC @ 1 mA
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8395)
Mechanical life: 2 × 10
7
cycles (300 cycles/min.)
R3-PD16 SPECIFICATIONS
ES-8395 Rev.6 Page 1/7
https://www.m-system.co.jp/