Remote I/O R3 Series ENCODER INPUT MODULE

R3-PA2W 数据手册

 浏览型号R3-PA2W的Datasheet PDF文件第2页浏览型号R3-PA2W的Datasheet PDF文件第3页浏览型号R3-PA2W的Datasheet PDF文件第4页浏览型号R3-PA2W的Datasheet PDF文件第5页 
MODEL: R3-PA2  
Remote I/O R3 Series  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input, Output: M3 separable screw terminal  
(torque 0.5 N·m)  
ENCODER INPUT MODULE  
(RS-422 input; alarm output)  
27.5 [1.08]  
Internal power: Via the Installation Base (model: R3-BSx)  
Screw terminal: Nickel-plated steel  
Isolation: Input 1 to input 2 to internal bus or internal power  
Alarm output: Two outputs per channel available; setpoints  
are programmable for the speed or the position data by  
using the R3CON PC Configurator software.  
DIP switch settings:  
130  
[5.12]  
109  
[4.29]  
•Input range  
•Count Mode  
mm [inch]  
•Alarm Contact Form  
•Start Count  
MODEL: R3-PA2[1][2]  
(Refer to the instruction manual)  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Green LED turns on in normal operating  
conditions.  
ORDERING INFORMATION  
• Code number: R3-PA2[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-PA2W/CE/Q)  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
Low-end cutout: 0.1 %  
Reset input: Position data reset to ‘0’ when the external  
contact is closed. (Reset count can be changed using the  
R3CON PC Configurator software.)  
NO. OF CHANNELS  
2: 2  
INPUT SPECIFICATIONS  
[1] COMMUNICATION MODE  
S: Single  
Input: RS-422 line driver, two-phase pulse (Up/down count is  
not performed correctly by either phase A or phase B input)  
ENCODER PULSE INPUT  
W: Dual  
Input range: 0 – 100 kHz, 0 – 10 kHz, 0 – 1 kHz, 0 – 100 Hz,  
0 – 10 Hz, 0 – 1 Hz, 0 – 0.1 Hz  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
Minimum pulse width requirement: 5 μsec. for both ON and  
OFF  
Reset Input (contact input)  
/CE: CE marking  
Number of input: 1 contact per input (2 in total)  
Isolation: Optical isolator + transformer (internal excitation  
supply)  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
Input resistance: Approx. 5.9 kΩ  
Common: Negative (2 terminals)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Sensing voltage: 13 V DC (max. 24 V with no load)  
ON current/voltage: ≥ 1.5 mA (≥ 9V)  
OFF current/voltage: ≤ 0.75 mA (≤ 4.5V)  
/C02: Polyurethane coating  
/C03: Rubber coating  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8386)  
R3-PA2 SPECIFICATIONS  
ES-8386 Rev.10 Page 1/5  
https://www.m-system.co.jp/  

与R3-PA2W相关器件

型号 品牌 获取价格 描述 数据表
R3-PA2W/CE MSYSTEM

获取价格

Remote I/O R3 Series ENCODER INPUT MODULE
R3-PA2W/Q MSYSTEM

获取价格

Remote I/O R3 Series ENCODER INPUT MODULE
R3-PA4 MSYSTEM

获取价格

Remote I/O R3 Series HIGH SPEED PULSE INPUT MODULE
R3-PA4A MSYSTEM

获取价格

Remote I/O R3 Series HIGH SPEED TOTALIZED PULSE INPUT MODULE
R3-PA4B MSYSTEM

获取价格

Remote I/O R3 Series LOW SPEED TOTALIZED PULSE INPUT MODULE
R3-PA4BS MSYSTEM

获取价格

Remote I/O R3 Series LOW SPEED TOTALIZED PULSE INPUT MODULE
R3-PA4BS/Q MSYSTEM

获取价格

Remote I/O R3 Series LOW SPEED TOTALIZED PULSE INPUT MODULE
R3-PA4BW MSYSTEM

获取价格

Remote I/O R3 Series LOW SPEED TOTALIZED PULSE INPUT MODULE
R3-PA4BW/Q MSYSTEM

获取价格

Remote I/O R3 Series LOW SPEED TOTALIZED PULSE INPUT MODULE
R3-PA4S MSYSTEM

获取价格

Remote I/O R3 Series HIGH SPEED PULSE INPUT MODULE