Series
PS
10-90Amp • 120/240 Vac - AC OUTPUT
•
•
•
•
Peak Switching
Panel Mount
600V Transient Capability
Internal Snubber
Input Status Indicator
Option Available
Output consists of an SCR AC switch turning ON
at the next peak of sinusoidal AC wave form after
the input has been activated. Continuing to
conduct normally until the input is de-activated
and then turning off at the next current zero cross
Suitable for switching of transformers and
other highly inductive loads where significant
inrush current may otherwise cause problems.
Manufactured in Crydom’s ISO 9001 Certified
facility for optimum product performance and
reliability.
•
Featuring state-of-the-art Surface Mount
Technology, these SPST-NO relays deliver
proven reliability in the most demanding
applications.
MODEL NUMBER
PSD2410
PSD2425
PSD2450
PSD2490
➀
OUTPUT SPECIFICATIONS
Operating Voltage (47-63 Hz) [Vrms]
Max. Load Current ➀ [Arms]
Min. Load Current, [mArms]
90-280
10
90-280
25
90-280
50
90-280
90
40
40
40
40
Transient Overvoltage [Vpk]
600
120
1.6
600
250
1.6
600
625
1.6
600
1200
1.6
Max. Surge Current, (16.6ms) [Apk]
Max. On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (R
) [˚C/W]
θJC
2
1.48
60
1.02
260
10
0.63
1620
10
0.28
6000
10
2
Maximum I t for Fusing, (8.3 msec.) [A sec]
Max. Off-State Leakage Current @ Rated Voltage [mArms]
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] ➀
Max. Turn-On Time
10
500
500
500
500
1/2 Cycle
Max. Turn-Off Time
1/2 Cycle
0.5
Power Factor (Min.) with Max. Load
0.5
0.5
0.5
INPUT SPECIFICATIONS➀
Control Voltage Range
Max. Reverse Voltage
Max. Turn-On Voltage
Min. Turn-Off Voltage
Nominal Input Impedance
Typical Input Current
3-32 Vdc
-32 Vdc
3.0 Vdc
1.0 Vdc
➀
See Note
➀
2mA
© 2003 CRYDOM CORP, Specifications subject to change without notice.
GENERAL NOTES
➀ All parameters at 25˚ C unless otherwise specified.
➀ Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
➀ Heat sinking required, for derating curves see page 3.
➀ Input circuit incorporates active current limiter.
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
SERIES PS
Rev. 111403
PAGE 1 OF 2