MODEL: MDW5ALW
DC Power
Lightning Surge Protectors for
Electronics Equipment M-RESTER
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
LIGHTNING SURGE PROTECTOR FOR
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
LonWorks
(life monitor)
APPLICABLE NETWORK
LonWorks FTT-10A network
Functions & Features
• Designed specifically for the network
• Life monitor function helps you to decide when you should
replace the surge protector
This unit is not applicable to LonWorks Link Power network.
GENERAL SPECIFICATIONS
Construction: Plug-in
• LED and alarm contact output indicate the degradation
and life span of the surge protection circuits
• Easy maintenance thanks to discharge elements installed
on the element module
Degree of protection: IP20 (If the solderless terminals are
covered with insulation tubes.)
Surge protection type: Two-port SPD
Connection
• No interruption of signal even unplugging head element
• DIN rail mounting
• Transmission, power & grounding: M3 screw terminals
(torque 0.8 N·m)
45 (1.78)
• Alarm output: Euro Type Connector Terminal
(torque 0.6 N·m)
Applicable wire size
Line, communication: See the 'External Dimensions.'
97 (3.82)
Alarm output: 0.2 to 2.5 mm2, stripped length 7 mm
Screw terminal
• Transmission, power & grounding: Nickel-plated steel
• Alarm output: Tin-plated copper alloy
Housing material: Flame-resistant resin (black)
Indicators
89 (3.5)
mm (inch)
• ALM: Green/Amber/Red tricolor LED
OFF when no surge is detected.
HEAD ELEMENT
MODEL: MDW5ALW–E
Green ON when surge is detected more than once.
Amber ON when element life is about to expire.
(Prepare to replace)
BASE
Red ON when element life is expired or deteriorated
or internal battery is drained. (Replace)
• PWR: Green LED
MODEL: MDW5ALW–B–[1]
ORDERING INFORMATION
Order the both pieces of this surge protector (the head
element and the base), respectively required for the use.
Order the pieces by separate only for replacement.
• Head element
ON when power is supplyed.
OFF when the base power circuit is in error.
Degradation judged: When the leakage current at the
voltage limiter exceeds approx. 100 μA
Life time judged: When the number of discharges of the
discharge element reaches the expected life span.
Alarm contact: Relay N.C contact
Code number: MDW5ALW-E
• Base
Code number: MDW5ALW-B-[1]
Specify a code from below for [1].
(e.g. MDW5ALW-B-R)
• Element error: ON when life span of the discharge
element has expired, the voltage limiter is degraded,
battery drain or element is removed.
• Base error: ON with power circuit error or power supply
failure
[1] POWER INPUT
AC Power
Rated load: 250 V AC @ 1 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
M2: 100 – 240 V AC (Operational voltage range 90 – 264 V,
47 – 66 Hz)
Maximum switching voltage: 264 V AC or 125 V DC
MDW5ALW SPECIFICATIONS
ES-8218 Rev.4 Page 1/5
http://www.m-system.co.jp/