MODEL: MDP-DM3
Lightning Surge Protectors for
Electronics Equipment M-RESTER
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
LIGHTNING SURGE PROTECTOR FOR MsysNet USE
Functions & Features
• Designed specifically for the network
• No interruption of transmission signal by unplugging the
head element module
INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN
rail mounting adapter
Lot.NO
MDEIJPAN1430B
PERFORMANCE
Max. continuous operating voltage (Uc):
B to C: ±5 V
M•STER
MODEL
B or C to A: 5 V
MODEL: MDP–DM3[1]
Line to earth: ±140 V
Voltage protection level (Up):
• @ 1 kV (100 A)
ORDERING INFORMATION
• Code number: MDP-DM3[1]
Specify a code from below for [1].
(e.g. MDP-DM3/A33/Q)
2 to 3: ±10 V
2 or 3 to 1: 10 V
Line to earth: ±650 V
• @ 2 kV (1 kA)
• Specify the specification for option code /Q
(e.g. /C01)
2 to 3: ±20 V
2 or 3 to 1: 20 V
Line to earth: ±800 V
Response time: ≤ 0.1 μsec.
Leakage current:
[1] OPTIONS (multiple selections)
DIN Rail Mounting Adapter
blank: Without
B to C: ≤ 0.2 mA @ ±5 V DC
B or C to A: ≤ 0.2 mA @ 5 V DC
Line to earth: ≤ 10 μA @ ±140 V DC
Max. discharge current (Imax): 5000 A (8 / 20 μs)
/A33: With adapter (model A-33)
Other Options
blank: none
/Q: Option other than the above (specify the specification)
Nominal current (I ): 100 mA
N
Internal series resistance: 4 Ω ±10 % (including return)
Capacitance @ 1 MHz:
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Line to line: ≤ 20 nF
Line to earth: ≤ 50 pF
Input attenuation: -0.5 dB or less @ DC to 100 kHz, Zo =
110 Ω
/C02: Polyurethane coating
/C03: Rubber coating
Surge protection: IEC 61643-21 Categories C1, C2, D1
RELATED PRODUCTS
• Repeater (model: DALx)
• Multi-transmission module (model: 22LAx)
• Multi-transmission unit (model: DLAx)
APPLICABLE NETWORK
SIN-NET (conform to RS-422), MsysNet, MsysNet-mini,
MuNet (RS-485), EC Cable (model ECx-5P)