MODEL: HDY2
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
Space-saving Plug-in Signal Conditioners H-UNIT
POWER INPUT
DC Power
CURRENT LOOP SUPPLY
(isolated)
R: 24 V DC
Functions & Features
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Powering a 4 – 20 mA DC current loop
• Shortcircuit protection
• Applicable to smart transmitters
• High-density mounting
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
Typical Applications
• Various 2-wire transmitters
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
26 (1.02)
/C02: Polyurethane coating
93
(3.66)
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
137
(5.39)
mm (inch)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
MODEL: HDY2–24[1]–R[2]
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
ORDERING INFORMATION
• Code number: HDY2-24[1]-R[2]
Specify a code from below for each of [1] and [2].
(e.g. HDY2-246-R/Q)
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
• Specify the specification for option code /Q
(e.g. /C01/S01)
SUPPLY OUTPUT
(across the terminals 1 – 2)
Output voltage:
SUPPLY OUTPUT
24: 24 V DC
24 – 28 V DC with no load
18 V DC min. at 20 mA
INPUT
Current
Current rating: ≤ 22 mA DC
• Shortcircuit Protection
Current limited: 30 mA max.
Protected time duration: No limit
4 – 20 mA DC (Input resistance 300 Ω)
[1] OUTPUT
Current
INPUT SPECIFICATIONS
■ DC Current: Input resistor incorporated
A: 4 – 20 mA DC (Load resistance 750 Ω max.)
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)
Voltage
INSTALLATION
Current consumption: Approx. 90 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting
Frame BX-16H available
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3: 0 – 1 V DC (Load resistance 1000 Ω min.)
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
HDY2 SPECIFICATIONS
ES-3427 Rev.3 Page 1/2
http://www.m-system.co.jp/