Forward and Reverse Operation of  
Single-phase Inductive Motors  
L
Motor  
C
Note: 1. The voltage between the load terminals of either SSR 1 or  
SSR 2 when turned OFF is approximately twice as high as  
the supply voltage due to LC coupling. Be sure to use an  
SSR model with a rated output voltage of at least twice the  
supply voltage. For example, if the motor operates at a sup-  
ply voltage of 100 VAC, the SSR must have an output volt-  
age of 200 VAC or higher.  
2. Make sure that there is a time lag of 30 ms or more to switch  
over SW1 and SW2.  
ON/OFF Control of Three-phase  
Inductive Motors  
Selecting an SSR for Different Loads  
The following provides examples of the inrush currents for different  
loads.  
Motor  
AC Load and Inrush Current  
Load  
R
Input signal  
source  
Three-  
phase  
power  
supply  
S
T
Resis-  
tive  
Capacitor  
Incan-  
descent  
lamp  
Solenoid  
Motor  
load  
Relay  
Inrush  
Approx. Approx. Approx. Approx. Approx. 1  
current/  
Normal  
current  
10 times 10 to 15 5 to 10 2 to 3  
times times times  
20 to 50  
times  
Forward and Reverse Operation of  
Three-phase Inductive Motors  
Wave-  
form  
Make sure that signals input into the individual SSRs are proper if the  
SSRs are applied to the forward and reverse operation of a three-  
phase motor. If SW1 and SW2 as shown in the following circuit dia-  
gram are switched over simultaneously, a phase short-circuit will  
result on the load side, which may damage the output elements of  
the SSRs. This is because the SSR has a triac as an output element  
that is turned ON until the load current becomes zero regardless of  
the absence of input signals into the SSR. Therefore, make sure that  
there is a time lag of 30 ms or more to switch over SW1 and SW2.  
The SSR may be damaged due to phase short-circuiting if the SSR  
malfunctions with noise in the input circuit of a SSR. To protect the  
SSR from phase short-circuiting damage, a protective resistance R  
may be inserted into the circuit.  
The value of the protective resistance R must be determined accord-  
ing to the withstanding inrush current of the SSR. For example, the  
G3NA-220B withstands an inrush current of 220 A. The value of the  
protective resistance R is obtained from the following.  
R > 220 V x 2/200A = 1.4 Ω  
Considering the circuit current and weld time, insert the protective  
resistance into the side that reduces the current consumption.  
Obtain the consumption power of the resistance from the following.  
P = I2R x Safety factor  
(I = Load current, R = Protective resistance, Safety factor = 3 to 5)  
832  
Solid State Relays Technical Information  

与G3J-205BLDC12-24相关器件

型号 品牌 获取价格 描述 数据表
G3J-211BL-2AC100-240 OMRON

获取价格

负载电流(mA):11.1 A;触头类型:SPST-NO(1 Form A);输出类型:A
G3J-211BLDC12-24 OMRON

获取价格

负载电流(mA):11.1 A;触头类型:SPST-NO(1 Form A);输出类型:A
G3J-S205BL OMRON

获取价格

Soft-start Solid State Contactors
G3J-S211BL OMRON

获取价格

Soft-start Solid State Contactors
G3J-S403BL OMRON

获取价格

Soft-start Solid State Contactors
G3J-S405BL OMRON

获取价格

Soft-start Solid State Contactors
G3J-T OMRON

获取价格

Soft-start/stop Function Starts and Stops Three-phase Motors Smoothly and Economically
G3J-T-C OMRON

获取价格

Solid State Contactor for 3-phase Motors with Built-in Soft Start/Stop and Monitor Output
G3J-T205BL OMRON

获取价格

Soft-start/stop Function Starts and Stops Three-phase Motors Smoothly and Economically
G3J-T205BL-C OMRON

获取价格

Solid State Contactor for 3-phase Motors with Built-in Soft Start/Stop and Monitor Output