5秒后页面跳转
FND-C PDF预览

FND-C

更新时间: 2024-09-16 02:52:15
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
3页 115K
描述
Plug-in Signal Conditioners M-UNIT

FND-C 数据手册

 浏览型号FND-C的Datasheet PDF文件第2页浏览型号FND-C的Datasheet PDF文件第3页 
MODEL: FND  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
DC Power  
S: 12 V DC  
R: 24 V DC  
V: 48 V DC  
Plug-in Signal Conditioners M-UNIT  
CURRENT LOOP SUPPLY  
(with square root extractor; non-isolated)  
Functions & Features  
• Powering a 4 – 20 mA DC current loop  
• Square root extraction  
P: 110 V DC (Not selectable with Option /E2.)  
• Shortcircuit protection  
• Applicable to smart transmitters  
• LCD meter (engineering unit display selectable)  
• Simple loop test output (0 % and 100 %)  
• High-density mounting  
[2] OPTIONS (multiple selections)  
LCD Meter (after function or low-end cutout)  
blank: Without  
/E: LCD meter (0.0 – 100.0 %)  
/E2: With LCD display in engineering unit  
with backlight and the simple loop test output  
Other Options  
Typical Applications  
• Various 2-wire transmitters  
• Square root extractor application (4 – 20 mA input)  
blank: none  
/Q: Option other than the above (specify the specification)  
50  
(1.97)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
80  
(3.15)  
/C02: Polyurethane coating  
/C03: Rubber coating  
127  
(5)  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
mm (inch)  
MODEL: FND–[1][2]  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
ORDERING INFORMATION  
•Code number: FND-[1][2]  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Specify a code from below for each [1] and [2].  
(e.g. FND-B/E2/Q)  
Housing material: Flame-resistant resin (black)  
Isolation: Input or output to power  
Overrange output: 0 – 105 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
Low-end cutout: Approx. 5 – 8 % (output)  
Simple loop test output: 0 % and 100 % signal simulated by  
selecting the front switch positions. (Only for option code  
/E2)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
INPUT  
Current  
4 – 20 mA DC (Input resistance 250 Ω)  
OUTPUT  
■ DISPLAY (LCD meter)  
Voltage  
• Option code: /E  
1 – 5 V DC (Load resistance 500 Ω min.)  
LCD digital display: 0.0 - 100.0 % (min. digit 0.1 %)  
(No scaling)  
• Option code: /E2  
[1] POWER INPUT  
AC Power  
LCD digital display: Engineering unit  
Display scaling: -10000 – +10000  
Decimal position: 10-1 - 10-4 or no decimal point  
Engineering unit: %, μV, mV, V, mA, A, °C, °F, Ω, DEG K,  
mHz, Hz, kHz, VAC, AAC, mg, g, kg, t, rpm or rps selectable  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
FND SPECIFICATIONS  
ES-3214 Rev.11 Page 1/3  
http://www.m-system.co.jp/  

与FND-C相关器件

型号 品牌 获取价格 描述 数据表
FND-C/E MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT
FND-C/E2 MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT
FND-C/Q MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT
FND-D MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT
FND-D/E MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT
FND-D/E2 MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT
FND-D/Q MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT
FNDDR1133 PERICOM

获取价格

3.3V CMOS Low-Jitter 133.330 MHz DDR XO
FND-F MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT
FND-F/E MSYSTEM

获取价格

Plug-in Signal Conditioners M-UNIT