DIN Rail Mount
DataSheet
• 10mm Single Channel DIN Rail Mount SSR Assembly
• AC Ratings up to 380 VAC and 10 Amps
DRA1 SPF Series
• 3-15 VDC, 15-32VDC, 18-36 VAC and 90-140 VAC Control
• Cage style screw terminals for easy connection
• Fits standard 35mm DIN rail
• Includes LED Status indicator (DC control only)
PRODUCT SELECTION
Control Voltage
3-15 VDC
10 A (Zero Voltage Turn-on)
DRA1-SPF240D25
10 A (Instantaneous Turn-on)
DRA1-SPF240D25R
DRA1-SPF380D25
DRA1-SPFE240D25
4-15 VDC
15-32 VDC
DRA1-SPF380D25R
DRA1-SPFE240D25R
18-36 VAC
DRA1-SPFE240A25
90-140 VAC
DRA1-SPF240A25
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage [VAC]
Transient Overvoltage [Vpk]
Maximum Load Current [Arms] (2)(3)
Minimum Load Current [Arms]
SPF(E)240x25
SPF380x25
48-380**
1200
10
12-280
600
10
0.06
0.06
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ maximum rated voltage [V/µsec] (4)
Maximum 1 Cycle Surge Current (50/60 Hz) [Apk]
0.1
500
239/250
0.1
500
239/250
Maximum I² t for Fusing (50/60 hz, 1/2 cycle) [A² sec]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
285/260
1.6
285/260
1.6
(1)
INPUT SPECIFICATIONS
Description
SPF240D25
SPF380D/480D
4-15 VDC
4.0 VDC
SPFE240D25
15-32 VDC
15 VDC
1.0 VDC
15 mA
1500 Ohm
1/2 Cycle
1/2 Cycle
SPF240A25
90-140 Vrms
90 Vrms
10 Vrms
10 mArms
14.1 k Ohm
10
SPFE240A25
Control Voltage Range
3-15 VDC
3.0 VDC
1.0 VDC
15 mA
18-36 VAC
18 Vrms
2 Vrms
10 mArms
2.1 k Ohm
10
Minimum Turn-On Voltage
Must Turn-Off Voltage
Typical Input Current
Nominal Input Impedance
Maximum Turn-On Time [msec] (5)
Maximum Turn-Off Time [µsec]
1.0 VDC
15 mA
240 Ohm
1/2 Cycle
1/2 Cycle
300 Ohm
1/2 Cycle
1/2 Cycle
40
40
GENERAL SPECIFICATIONS (1)
Description
Dielectric Strength, Input/Output (50/60Hz)
Minimum Insulation Resistance (@ 500 VDC)
Parameters
4000 Vrms
109 Ohms
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
8 pF
-30 to 80 °C
-30 to 125 °C
0.32 lb oz (145.5 g)
Thermally conductive Epoxy
Encapsulation
GENERAL NOTES
(1) All parameters at 25°C unless otherwise specified.
(2) See derating chart on page 3.
(3) Steady state load current exceeding 10 Amps will damage socket.
(4 Off-state dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
(5) Turn-On Time for DC control instantaneous turn-on versions is 0.1 msec.
** NOTE: Voltages in excess of 380V will damage output terminals.