DC Current transducer DK-B020/420
IPN = 50 .. 400 A
A split core transducer for the electronic measurement DC current,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit) with current output.
Electrical data
Features
Primary Nominal Current Analogue Output Signal1)
Types
RoHS
· DC Measurement
· Split core box
IPN (A.t)
50,75,100
IOUT (mA)
0-20
Date Code
DK 100 B020 MAY 2006
DK 200 B020 planned
DK 300 B020 planned
DK 400 B020 planned
DK 100 B420 planned
DK 200 B420 MAY 2006
DK 300 B420 planned
DK 400 B420 planned
· Current output
100,150,200
150,225,300
200,300,400
50,75,100
0-20
· Jumper selectable ranges
· Panel mounting
0-20
0-20
· Extended measuring range
4-20
100,150,200
150,225,300
200,300,400
4-20
4-20
Advantages
4-20
· Large aperture
Vc
RL
Vb
Vd
f
Supply voltage
20-50 V DC
22-38
650 max.
150
V AC
W
· High isolation between primary and
secondary circuits
Load resistance (max)
Rated voltage(CAT III, PD2)
Isolation voltage
V AC
V
· Easy to mount
3000
DC
· No insertion losses
Frequency
Ic
Current consumption(max)
100
mA
Applications
Accuracy - Dynamic performance data
X
Accuracy @ IPN, TA=25°C
DK 300 BXX
± 1
%
%
· Battery Banks
± 1.5
± 2
- Monitors load current
- Monitors charging current
- Verifies operation
DK 400 BXX
%
eL
Linearity error
± 0.75
< 100
%
tr
Response time @ 90% of IPN
mS
· Transportation
Measures traction power or auxiliary
loads
General data
TA
TS
m
Ambient operating temperature (0-95% RH)
Ambient storage temperature
Mass
- 20 .. + 50
- 20 .. + 85
°C
°C
g
· Electric Heating Elements
Faster response than temperature
sensors
120
IPXX Protection type
IP 20
Safety
EMC
IEC 61010-1
EN 61326 2)
Options on request
· DIN mounting
Notes : 1) For 0-20 mA and 4-20 mA outputs models, no saturation outputs up to 23 mA
Application domain
· Industrial.
2)
For IEC 61000-4-3, IEC 61000-4-6 and IEC 61000-4-4 Criterion B :
temporary impairment to operational behavior.
Remark : Temperature of the primary conductor should not exceed 60°C.
060616/11
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
page 1/2
LEM Components
www.lem.com