Voltage Sensitive Relays
WILMAR™ Protective Relays – D100X Series, Close Differential
Function:
• ANSI/IEEE C37.90-1978
• UL file No. E58048
• CSA file No. LR61158
Close Differential Relays are voltage sensitive. The
pick-up and drop-out voltage settings are indepen-
dently adjustable, which allows precise setting of the
differential voltage. This relay is available in a wide
range of AC and DC voltages. Their primary applica-
tion is the sensing and control of transfer switches.
0.5
Operation:
See Part Number
Selection
Monitors a single phase AC signal, and is used for
undervoltage detection. Has separate pick-up and
drop-out voltage settings, providing an adjustable
hysteresis.
2.6
3.06
3.5
2.250
3
11
/64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PRODUCT SPECIFICATIONS
PART NUMBER SELECTION
Sample Part No.
D100X
Part Number
D100X
Nominal Voltage ............................... AC, Single Phase, see part number selection
Nominal Frequency .......................... 50 to 400 Hz.
Model: L-L Volts
D100X = 120 VAC
Height
2"
D100-6X = 120 VAC, Spike Suppression
D100-3X = 208 VAC
2"
Pick-Up Adjustment Range ............. 67-100% of nominal voltage
Drop-Out Adjustment Range ........... 67-100% of nominal voltage
Maximum Differential Setting.......... 33% of nominal voltage
Minimum Differential Setting .......... 2% of nominal voltage
Output Contacts ............................... Form C (SPDT)
3.125"
3.125"
3.125"
3.125"
3.125"
D100-4X = 240 VAC
D100-8X = 277 VAC
D100-5X = 480 VAC
D100-7X = 510 VAC
Surge Withstand Capability is in compliance with the
requirements of ANSI/IEEE C37.90B
Contact Ratings ................................ 5 Amp resistive at 120 VAC or 28 VDC
Operating Temperature Range ........ -20°C to +85°C
Notes:
Expected Life .................................... 10 million operations
1. Remove black nylon protective screws to gain
access to the two internal adjustment
potentiometers.
2. Clockwise rotation of the pick-up and drop-out
adjustment will raise the voltage trip point.
3. The relay contacts are shown in the de-energized
state.
Inverse Time Drop-Out: The differential relay contains a time delay before operation so that
momentary voltage transients do not aftect the operation of the relay. The time delay has an
inverse time characteristic so that excessive voltage conditions will cause a more rapid drop-
out. This time delay is approximately 200mSec. (12 cycles) at the trip settings and
decreases to 30 mSec. at approximately 15% beyond the trip settings.
Consult factory for additional models.
2 6