CTR Series
• Ratings 25 A per phase @ 600 VAC
• DIN-RAIL or Panel Mount 90mm (width) package
• UL 508 Endurance Rating for Enhanced Reliability
• SCR output for heavy industrial loads
• Overvoltage Protection Built in (Internal TVS)
• LED input Status indicator
• AC or DC control
• Zero voltage or instantaneous turn-on output
• UL Recognized, CE, RoHS and EMC Compliant
PRODUCT SELECTION
Control Voltage
4-32 VDC Control
90-140 VAC Control
180-280 VAC Control
25 A
CTRD6025
CRTB6025
CTRC6025
AVAILABLE OPTIONS
Control Voltage
B: 90 to 140 VAC
C: 180 to 280 VAC
D: 4 to 32 VDC
Output Rating
25: 25 Amps/phase
Series
CTR
D
60
25 -10
CTR: Standard 3 phase
90 mm DIN rail mount
SSR package
Thermal Pad
Line Voltage Rating
60: 48 to 600 VAC
Blank: Zero Voltage
Turn-On
Turn-On
-10: Instantaneous
Required for valid part number
For options only and not required for valid part number
Not all part number combinations are available.
Contact Crydom Technical Support for information on
the availability of a specific part number.
*
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-63Hz) [VRMS]
Transient Overvoltage [Vpk]
Maximum Load Current [Arms] (2)
Minimum Load Current [Arms]
CTRx6025
48-600
1100
25
0.1
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (3)
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk]
Maximum I² t for Fusing (50/60Hz, 1/2 cycle ) [A² sec]
UL/IEC 60947 Motor Control Rating @ 240V [HP/KW] (4)
UL/IEC 60947 Motor Control Rating @ 380V [HP/KW] (4)
UL/IEC 60947 Motor Control Rating @ 480V [HP/KW] (4)
Minimum Power Factor (with Maximum Load)
Min/Max stranded wire
0.25
500
1.35
286/300
410/374
1/0.74
2/1.48
3/2.22
0.5
16/8 AWG
16/10 AWG
Min/Max solid wire
Do not forget to visit us at: www.crydom.com