Catalog 1308242
Issued 3-03
P&B
CH series
Mid- To Low -Priced
CMOS IC Tim e Delay Relay
• Choice of timing modes
– Delay on operate
– Delay on release
– Interval on
• Fixed or knob adjustable types
• 10A output relay with DPDT contacts
• Various models time from 1 to 180 sec.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Contact Data @ 25°C
Tim ing Modes
Arrangem ents: 2 Form C (DPDT).
Material: Silver-cadmium oxide alloy.
Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC; 1/3 HP @
120VAC.
Delay on operate – Delay period begins when input voltage is applied. At
the end of the delay period, the relay will operate and will not release until
input voltage is removed. Reset occurs when input voltage is reapplied.
INPUT
VOLTAGE
ON
OFF
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 100,000 operations, min., at rated load.
N.O. RELAY ON
CONTACTS OFF
TIME
Initial Dielectric Strength
Betw een Open Contacts: 500V rms, 60 Hz.
Betw een All Other Conductors: 500V rms, 60 Hz.
Delay on release – Input voltage must be applied continuously to operate
the internal relay. When the control switch is closed, the relay energizes.
When the control switch is opened, timing begins. When timing is
complete, the relay will de-energize. Time may be reset to zero during
timing by closing the control switch.
Input Data @ 25°C
Voltage: 24 through 240VAC and 24VDC.
Pow er Requirem ent: AC Types: Typically less than 3 VA.
DC Types: Typically less than 3 W.
CONTROL
SWITCH
ON
OFF
N.O. RELAY ON
CONTACTS OFF
TIME
Transient Protection: Yes.
Reverse Voltage Protection: Yes.
Input Voltages & Lim its @ 25°C
Voltage
Type
Nom inal
Voltage
Minim um
Voltage
Maxim um
Voltage
Interval on – The relay energizes and timing begins when input voltage is
applied. At the end of the time delay period the relay will de-energize.
Reset is accomplished by removing, then reapplying, the input voltage.
AC
DC
24
120
240
20
105
210
28
130
260
INPUT
ON
VOLTAGE
OFF
24
20
32
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
N.O. RELAY ON
CONTACTS OFF
AC models will operate on 50 or 60 Hz.
TIME
Environm ental Data
Tim ing Specifications
Tim ing Ranges: From 1 to 180 sec.
Tem perature Range: Storage: -55°C to +85°C.
Operating: -10°C to +55°C.
Tim ing Adjustm ent: Fixed and knob adjustable.
Tolerance (for AC units add ±1/2 cycle 60 Hz.):
Knob Adj. Types:–0, +20% of max. specified at high end of timing range;
min. specified, or less, at low end.
Mechanical Data
Fixed Types:
±5% .
Term ination: 8- or 11-pin octal style plug.
Res. Adj. Types: ±5% at high end of timing range; min. specified, or less,
at low end.
Enclosure: White plastic case. Knob adjustable types have dial scale for
reference only.
Delta Tim e (for AC units add ±1 cycle 60 Hz.): ±10% .
Repeatability (for AC units add ±1 cycle 60 Hz.): ±2% .
Release Tim e: 125 ms, typ.; 200 ms, max.
Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
screw terminal sockets. 11-pin types fit either 27E123 or
27E892 (snap-on) screw terminal sockets.
Recycle Tim e: 125 ms, typ.; 200 ms, max.
Weight: 6 oz. (170g) approximately.
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.