MODEL: 60D
Field Network Modules 60-UNIT Series
[4] OPTIONS
blank: none
/Q: With options (specify the specification)
ANALOG I/O MODULE
(DeviceNet)
Functions & Features
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK
modules with DeviceNet
• Saving power and I/O wiring inside an instrumentation
panel
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
72
(2.83)
80
(3.15)
RELATED PRODUCTS
•Special cable (model: MCN34)
• Programming Unit (model: PU-2x)
153
(6.02)
GENERAL SPECIFICATIONS
Construction: Plug-in
mm (inch)
Connection
DeviceNet: Euro type connector terminal (applicable
MODEL: 60D-[1][2]-[3][4]
wire size: 0.2 to 2.5 mm , stripped length 7 mm)
2
I/O: 34-pin connector (OMRON XG4A-3434)
Power input: M3.5 screw terminal
ORDERING INFORMATION
• Code number: 60D-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. 60D-161-K/Q)
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to DeviceNet to power to FG1
Power indicator: Green LED turns on with power supplied.
• Specify the specification for option code /Q
(e.g. /C01/S01)
DeviceNet COMMUNICATION
Transmission cable: Approved for DeviceNet
Node address setting: DIP switch; 00 – 63
Baud rate setting: DIP switch
[1] NO. OF CHANNELS
04: 4 points
08: 8 points
16: 16 points
MS (Module Status) indicator: Bi-color (green/red) LED
indicates device status.
[2] I/O TYPE
1: Input
NS (Network Status) indicator: Bi-color (green/red)
LED indicates status of the communication link.
2: Output
INPUT SPECIFICATIONS
■ Analog Input
[3] POWER INPUT
AC Power
Input range: 1 – 5 V DC
K: 85 – 132 V AC
Input resistance: ≥ 1 MΩ
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
(CE not available)
DC Power
R: 24 V DC
A/D conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal 0000
– 1770 (0 – 6000). -15 to 0 % is represented by 2’s
complements.
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Overall range is represented by hexadecimal FC7C – 1AF4
60D SPECIFICATIONS
ES-6604 Rev.15 Page 1/4
https://www.m-system.co.jp/