MODEL: R7F4HEIP-DAC16B
Remote I/O R7F4HEIP Series
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
EtherNet/IP I/O MODULE
(NPN discrete input, PNP transistor output, 8 points each,
/C02: Polyurethane coating
/C03: Rubber coating
tension clamp terminal block)
Functions & Features
• 8 points NPN discrete input, 8 points PNP transistor output
module for EtherNet/IP
RELATED PRODUCTS
• PC configurator software (model: R7CFG)
• Supports DLR (Device Level Ring) to form a ring topology
• EDS file
The EDS file and configurator software are downloadable at
M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
115 [4.53]
55 [2.17]
GENERAL SPECIFICATIONS
Connection
72 [2.83]
mm [inch]
EtherNet/IP: RJ-45 Modular Jack
Power supply, exc. supply, I/O: Tension clamp terminal
Housing material: Flame-resistant resin (gray)
Isolation: Input or exc. supply to output or exc. supply to
EtherNet/IP or FE to power
MODEL: R7F4HEIP-DAC16B-4-R[1]
Output at the loss of communication: Configurable via
R7CFG
ORDERING INFORMATION
• Code number: R7F4HEIP-DAC16B-4-R[1]
Specify a code from below for [1].
(e.g. R7F4HEIP-DAC16B-4-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
Status indicator LED: PWR, LNK1, LNK2
(Refer to the instruction manual)
Discrete I/O status indicator LED: Green LED turns on with
I/O ON
Read rate: Selectable with R7CFG
I/O TYPE
DAC16B: NPN discrete input &
EtherNet/IP COMMUNICATION
Communication Standard: IEEE 802.3u
Transmission: 10BASE-T, 100BASE-TX
Baud rate: 10/100 Mbps (Auto Negotiation function)
Protocol: EtherNet/IP
PNP transistor output, 8 points each
TERMINAL BLOCK: 4
Max. number of socket connections: 3
Connection type: Exclusive owner / Listen only / Input only
Transmission media: 10BASE-T (STP, Category 5), 100BASE-
TX (STP, Category 5e)
Tension clamp terminal block for power supply
RJ-45 Modular jack for communication
Tension clamp terminal block for I/O
Network topology: Line, star and ring
Max. length of fieldbus segment: 100 meters
IP address: 192.168.0.250 (factory setting);
Only host address in IP address is configurable via rotary
switches, the other items via PC configurator software
(model: R7CFG).
POWER INPUT
DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)
[1] OPTIONS
DLR supported
blank: none
Port No.: 2222, 44818
/Q: With options (specify the specification)
I/O data size: One (1) word
Status indicator LEDs: MS, NS (Refer to the instruction
manual for details)
R7F4HEIP-DAC16B SPECIFICATIONS
ES-8005-D Rev.0 Page 1/5
https://www.m-system.co.jp/