MODEL: R7F4HEIP-DC16A
Remote I/O R7F4HEIP Series
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
EtherNet/IP I/O MODULE
(NPN transistor output, 16 points, tension clamp terminal
block)
/C02: Polyurethane coating
/C03: Rubber coating
Functions & Features
• 16 points NPN transistor output module for EtherNet/IP
• Supports DLR (Device Level Ring) to form a ring topology
RELATED PRODUCTS
• PC configurator software (model: R7CFG)
• EDS file
The EDS file and configurator software are downloadable at
M-System’s web site.
115 [4.53]
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
55 [2.17]
GENERAL SPECIFICATIONS
Connection
72 [2.83]
mm [inch]
EtherNet/IP: RJ-45 Modular Jack
Power supply, exc. supply, output: Tension clamp terminal
Housing material: Flame-resistant resin (gray)
Isolation: Output or exc. supply to EtherNet/IP or FE to
power
MODEL: R7F4HEIP-DC16A-4-R[1]
ORDERING INFORMATION
• Code number: R7F4HEIP-DC16A-4-R[1]
Specify a code from below for [1].
(e.g. R7F4HEIP-DC16A-4-R/Q)
Output at the loss of communication: Configurable via
R7CFG
Status indicator LED: PWR, LNK1, LNK2
(Refer to the instruction manual)
Discrete output status indicator LED: Green LED turns on
with output ON
• Specify the specification for option code /Q
(e.g. /C01)
I/O TYPE
DC16A: NPN transistor output, 16 points
EtherNet/IP COMMUNICATION
Communication Standard: IEEE 802.3u
Transmission: 10BASE-T, 100BASE-TX
Baud rate: 10/100 Mbps (Auto Negotiation function)
Protocol: EtherNet/IP
TERMINAL BLOCK: 4
Tension clamp terminal block for power supply
RJ-45 Modular jack for communication
Tension clamp terminal block for I/O
Max. number of socket connections: 3
Connection type: Exclusive owner / Listen only / Input only
Transmission media: 10BASE-T (STP, Category 5), 100BASE-
TX (STP, Category 5e)
POWER INPUT
DC power
Network topology: Line, star and ring
Max. length of fieldbus segment: 100 meters
IP address: 192.168.0.250 (factory setting);
Only host address in IP address is configurable via rotary
switches, the other items via PC configurator software
(model: R7CFG).
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)
[1] OPTIONS
blank: none
DLR supported
/Q: With options (specify the specification)
Port No.: 2222, 44818
I/O data size: One (1) word
Status indicator LEDs: MS, NS (Refer to the instruction
manual for details)
R7F4HEIP-DC16A SPECIFICATIONS
ES-8005-B Rev.0 Page 1/5
https://www.m-system.co.jp/