MODEL: R3-NP1
Remote I/O R3 Series
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
PROFIBUS-DP INTERFACE MODULE
/C02: Polyurethane coating
27.5 [1.08]
/C03: Rubber coating
CAUTION
■ Mounting on 2-slot base
130
[5.12]
Use a dedicated base (R3-BS02P) for R3-NP1.
115.1
[4.53]
GENERAL SPECIFICATIONS
Connection
mm [inch]
PROFIBUS: 9-pin D-sub connector, female
Internal bus: Via the Installation Base (model: R3-BSx)
Internal power: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output: M3 separable screw
terminal (torque 0.5 N·m)
MODEL: R3-NP1-[1][2]
ORDERING INFORMATION
• Code number: R3-NP1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NP1-R/CE/Q)
Screw terminal: Nickel-plated steel
Isolation: PROFIBUS to internal bus or internal power to
power supply to RUN contact output to FG
Input error data setting: Input value setting at input module
error with side DIP SW
• Specify the specification for option code /Q
(e.g. /C01)
Dual communication setting: Set with the side DIP switch
RUN indicator: Bi-color (green/Amber) LED
(Function selected with DIP SW)
[1] POWER INPUT
N: No power supply
ERR indicator: Bi-color (green/red) LED
(Function selected with DIP SW)
AC Power
■ RUN CONTACT OUTPUT
K3: 100 – 120 V AC
RUN contact: Turns ON while the green RUN LED is ON.
(PROFIBUS in normal communication)
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *
(CE not available)
L3: 200 – 240 V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *
(CE not available)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or
network modules with the internal power input options.
Mechanical life: 2 × 10 cycles (300 cycles/min.)
7
When driving an inductive load, external contact protection
and noise quenching recommended.
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
PROFIBUS COMMUNICATION
Interface: PROFIBUS-DP, slave (RS-485 isolation)
Max. baud rate: 12 Mbps
/CE: CE marking
Protocol: DPV1
Other Options
Station No. setting: Rotary switch; 00 - 7D
(Address is 7D even setting greater value)
GSD file: Msys093F.GSD
blank: none
/Q: Option other than the above (specify the specification)
GSD files are downloadable at M-System’s web site or at
PROFIBUS International site (www.profibus.com).
Input data: Max. 240 bytes
Output data: Max. 240 bytes
R3-NP1 SPECIFICATIONS
ES-8418 Rev.15 Page 1/5
https://www.m-system.co.jp/