5秒后页面跳转
NISCXI-1167 PDF预览

NISCXI-1167

更新时间: 2024-11-05 12:19:59
品牌 Logo 应用领域
美国国家仪器公司 - NI 驱动器继电器
页数 文件大小 规格书
3页 182K
描述
64-Channel External Relay Driver

NISCXI-1167 数据手册

 浏览型号NISCXI-1167的Datasheet PDF文件第2页浏览型号NISCXI-1167的Datasheet PDF文件第3页 
64-Channel External Relay Driver  
NEW  
NI PXI-2567, NI SCXI-1167  
• Controls up to 64 single-side stable  
relays (or 32 2-coil latching relays)  
• Accepts internal and external power  
Up to 50 V  
Up to 600 mA per channel  
• High-power protection circuitry  
• Hardware or software scanning  
• 32,000-step scan list for deterministic  
scanning  
Operating Systems  
• Windows 2000/NT/XP  
Recommended Software  
• LabVIEW™  
• LabWindows/CVI™  
• Measurement Studio  
• NI Switch Executive  
Other Compatible Software  
• Visual Basic  
• Programmable switching delay  
• C/C++  
Applications  
• High-current relays  
• RF relays  
Driver Software (included)  
• NI-SWITCH  
• Small DC motors  
• Existing embedded relays  
Overview  
Automatic Scanning  
The National Instruments PXI-2567 and SCXI-1167 are designed to The PXI-2567 and SCXI-1167 are able to maximize throughput in  
be 64-channel, multipurpose relay drive modules, capable of driving automated test applications by the use of scanning. Scanning  
many types of external relays. The relay driver is the ideal choice improves throughput by downloading a list of up to 32,000  
when the current and voltage requirements for relays exceed those connections to the switch modules and cycling through the list using  
found in existing relay modules (or for relays embedded in a test an event (trigger) without any interruption from the host processor.  
system). High-current, high-voltage, or multipole RF switches all fit Scanning is most efficiently accomplished by mating the PXI-2567 or  
into the realm of possibilities. The NI PXI-2567 and NI SCXI-1167 SCXI-1167 with an instrument, such as the NI PXI-4070 FlexDMM,  
can also drive small DC motors or other inductive relay coils.  
that issues a trigger after each measurement.  
Internal and External Power Support  
Software  
The PXI-2567 and SCXI-1167 can provide up to 50 V or 600 mA of All National Instruments PXI and SCXI switch modules are shipped  
drive capacity per channel when connected to an external power with NI-SWITCH, an IVI-compliant driver offering complete  
supply. Without an external power supply, the PXI-2567 can source functionality for all switch modules. For additional assistance in  
up to 1.25 A from the 5 V pin or 500 mA from the 12 V pin provided configuring, programming, and managing higher-channel-count  
by the PXI backplane. The SCXI-1167 can supply up to 750 mA at switching systems, NI Switch Executive software offers an easy-to-use  
5 V without an external power source. No one channel can drive intelligent switch management and visual routing environment.  
more than 600 mA with either an internal or external source, and  
total module current is limited to 25 A of simultaneous drive.  
Protection Circuitry  
The eight banks of eight drivers in the PXI-2567 and SCXI-1167  
protect against overvoltage and overcurrent conditions. When the  
condition clears, the channel is automatically reset so no disassembly  
of the module is required. A fly-back diode is also included to protect  
against damage from inductive loads.  

与NISCXI-1167相关器件

型号 品牌 获取价格 描述 数据表
NISCXI-1190 NI

获取价格

4x1 unterminated multiplexer/50 characteristic impedance
NISCXI-1191 NI

获取价格

4x1 unterminated multiplexer/50 characteristic impedance
NISCXI-1193 NI

获取价格

500 MHz bandwidth/50 OHM characteristic impedance
NISCXI-1195 NI

获取价格

5 GHz 4x1 and Quad 4x1 Multiplexers
NISCXI-1306 NI

获取价格

SCXI 16-Channel RTD Module
NISCXI-1503 NI

获取价格

SCXI 16-Channel RTD Module
NISCXI1521 NI

获取价格

SCXI Quarter-Bridge Strain Gage Input Module
NISCXI-1521 NI

获取价格

SCXI Quarter-Bridge Strain Gage Input Module
NISCXI-1521B NI

获取价格

24 quarter-bridge strain gage inputs/Programmable excitation
NISR10JTR NICHICON

获取价格

General Purpose Inductor, 0.1uH, 5%, 1 Element, Alumina-Core, SMD