MODEL: MD6T-24
which the surge protector is used.
Lightning Surge Protectors for
Electronics Equipment M-RESTER
GENERAL SPECIFICATIONS
Degree of protection: IP65
LIGHTNING SURGE PROTECTOR FOR
Wiring conduit: See ‘Ordering information.’
Connection
STANDARD SIGNAL LINE & PULSE USE
(conduit mount, weather-proof, 24 V DC line voltage)
Functions & Features
Cable side: Euro type terminal block (Applicable wire size:
0.14 – 1.5 mm (AWG26 – 16) for both stranded and solid
2
• Designed specifically for 4 – 20 mA DC and
pulse signal line including both 4-wire and 2-wire
transmitters
wires; stripped length 6 mm)
Equipment side: Leadwires (leadwire diameter AWG20 for
grounding; AWG22 for the protected equipment)
Body material: Nickel-plated brass or stainless steel 316
• Direct mount in a wiring conduit of outdoor enclosures
• Absorbs surges only without affecting instrumentation
signal
INSTALLATION
Operating temperature:
No Safety approval: -40 to +85°C (-40 to +185°F)
ATEX approval:
-40 to +80°C (-40 to +176°F) (T5)
-40 to +75°C (-40 to +167°F) (T6)
Mounting: Screwed into an electrical conduit of outdoor
enclosures
Weight: 500 g (1.1 lb)
PERFORMANCE
MODEL: MD6T–24–[1][2][3]
Discharge voltage (peak voltage)
Line to line: 30 V min.
ORDERING INFORMATION
• Code number: MD6T–24–[1][2][3]
Specify a code from below for each of [1] through [3].
(e.g. MD6T-24-00B)
Line to ground: ±160 V min.
Max. surge voltage
Line to line: 40 V max.
Line to ground: ±650 V max.
(The maximum voltage that could pass through the surge
protector. Protected equipment must be able to withstand
this voltage for a very short time period.)
Response time:
For the safety approval code 4, specify the product’s
destination country using Ordering Information Sheet (No.
ESU-8284).
[1] SAFETY APPROVAL
0: None
Line to line: ≤ 4 nsec.
Line to ground: ≤ 20 nsec.
4: ATEX flameproof
Leakage current:
Line to line: ≤ 5 μA @ 30 V DC
Line to ground: ≤ 5 μA @ ±160 V DC
Discharge current capacity: 10000 A (8/ 20 μsec.)
Max. load current: 100 mA
[2] WIRING CONDUIT
0: G 1/2 (Not selectable for ATEX flameproof approval)
1: 1/2 NPT
Internal series resistance: Approx. 22 Ω including return
Max. line voltage
2: M20 × 1.5
Without safety approval: 30 V DC
With safety approval: 28 V DC
Capacitance @ 1 kHz:
[3] BODY MATERIAL
B: Brass
S: Stainless steel
Line to line: ≤ 2500 pF
Line to ground: ≤ 100 pF
CAUTION
The packing of the cable gland must be separate from the
body. Choose an appropriate one for the environment in
MD6T-24 SPECIFICATIONS
ES-8283 Rev.9 Page 1/3
http://www.m-system.co.jp/