5秒后页面跳转
MD6T-65-42S PDF预览

MD6T-65-42S

更新时间: 2024-11-13 02:49:03
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
3页 118K
描述
Lightning Surge Protectors for Electronics Equipment M-RESTER

MD6T-65-42S 数据手册

 浏览型号MD6T-65-42S的Datasheet PDF文件第2页浏览型号MD6T-65-42S的Datasheet PDF文件第3页 
MODEL: MD6T-65  
which the surge protector is used.  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
GENERAL SPECIFICATIONS  
Degree of protection: IP65  
LIGHTNING SURGE PROTECTOR FOR  
Wiring conduit: See ‘Ordering information.’  
Connection  
STANDARD SIGNAL LINE & PULSE USE  
(conduit mount, weather-proof; 65 V DC line voltage)  
Functions & Features  
Cable side: Euro type terminal block (Applicable wire size:  
0.14 – 1.5 mm (AWG26 – 16) for both stranded and solid  
2
• Designed specifically for 4 – 20 mA DC and pulse signal  
line including both 4-wire and 2-wire transmitters  
• Direct mount in a wiring conduit of outdoor  
enclosures  
wires; stripped length 6 mm)  
Equipment side: Leadwires (leadwire diameter AWG20 for  
grounding; AWG22 for the protected equipment)  
Body material: Nickel-plated brass or stainless steel 316  
• Absorbs surges only without affecting instrumentation  
signal  
INSTALLATION  
Operating temperature:  
No Safety approval: -40 to +85°C (-40 to +185°F)  
ATEX approval:  
-40 to +80°C (-40 to +176°F) (T5)  
-40 to +75°C (-40 to +167°F) (T6)  
Mounting: Screwed into an electrical conduit of outdoor  
enclosures  
Weight: 500 g (1.1 lb)  
PERFORMANCE  
MODEL: MD6T–65–[1][2][3]  
Discharge voltage (peak voltage)  
Line to line: 70 V min.  
ORDERING INFORMATION  
• Code number: MD6T–65–[1][2][3]  
Specify a code from below for each of [1] through [3].  
(e.g. MD6T-65-00B)  
Line to ground: ±160 V min.  
Max. surge voltage  
Line to line: 100 V max.  
Line to ground: ±650 V max.  
(The maximum voltage that could pass through the surge  
protector. Protected equipment must be able to withstand  
this voltage for a very short time period.)  
Response time:  
For the safety approval code 4, specify the product’s  
destination country using Ordering Information Sheet (No.  
ESU-8284).  
[1] SAFETY APPROVAL  
0: None  
Line to line: ≤ 4 nsec.  
Line to ground: ≤ 20 nsec.  
4: ATEX flameproof  
Leakage current:  
Line to line: ≤ 5 μA @ 70 V DC  
Line to ground: ≤ 5 μA @ ±160 V DC  
Discharge current capacity: 10000 A (8/ 20 μsec.)  
Max. load current: 100 mA  
[2] WIRING CONDUIT  
0: G 1/2 (Not selectable for ATEX flameproof approval)  
1: 1/2 NPT  
Internal series resistance: Approx. 22 Ω including return  
Max. line voltage  
2: M20 × 1.5  
Without safety approval: 70 V DC  
With safety approval: 66 V DC  
Capacitance @ 1 kHz:  
[3] BODY MATERIAL  
B: Brass  
S: Stainless steel  
Line to line: ≤ 2500 pF  
Line to ground: ≤ 100 pF  
CAUTION  
The packing of the cable gland must be separate from the  
body. Choose an appropriate one for the environment in  
MD6T-65 SPECIFICATIONS  
ES-8280 Rev.3 Page 1/3  
http://www.m-system.co.jp/  

与MD6T-65-42S相关器件

型号 品牌 获取价格 描述 数据表
MD6X ETC

获取价格

CABLE MIDI-DIN 5PIN BLACK 6FT
MD6Z12WEBSE-HAF SWST

获取价格

稳压二极管
MD6Z12WE-HAF SWST

获取价格

稳压二极管
MD6Z13WEBSE-HAF SWST

获取价格

稳压二极管
MD6Z15WEBSE-HAF SWST

获取价格

稳压二极管
MD6Z16WEBSE-HAF SWST

获取价格

稳压二极管
MD6Z18WEBSE-HAF SWST

获取价格

稳压二极管
MD6Z20WEBSE-HAF SWST

获取价格

稳压二极管
MD6Z22WEBSE-HAF SWST

获取价格

稳压二极管
MD6Z24WEBSE-HAF SWST

获取价格

稳压二极管