Current Transducer LA 125-P
IPN = 125 A
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
IPN
IP
RM
Primary nominal r.m.s. current
Primary current, measuring range
Measuring resistance @
125
0 .. ± 200
TA = 70°C
RM min RMmax RM min RMmax
A
A
Features
TA = 85°C
· Closed loop (compensated) current
transducer using the Hall effect
· Printed circuit board mounting
· Insulated plastic case recognized
according to UL 94-V0.
with ± 12 V
with ± 15 V
@ ± 125 A max
5
5
52
20
25 74
25 34
14
14
40
50
18
72
W
W
W
W
@ ± 200 A max
@ ± 125 A max
@ ± 200 A max
401) 40 1)
Advantages
ISN
KN
VC
IC
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
125
1 : 1000
± 12 .. 15
16 (@ ±15 V)+IS mA
mA
· Excellent accuracy
· Very good linearity
V
· Low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
Vd
3
kV
Accuracy - Dynamic performance data
X
Accuracy @ IPN , TA = 25°C
@ ± 15 V (± 5 %)
± 0.60
± 0.80
< 0.15
%
%
%
@ ± 12 .. 15 V (± 5 %)
e
Linearity
· Current overload capability.
L
Typ
Max
Applications
IO
IOM
IOT
Offset current @ IP = 0, TA = 25°C
± 0.40 mA
± 0.50 mA
± 0.15 ± 0.50 mA
± 0.15 ± 0.60 mA
Residual current 2) @ IP = 0, after an overload of 3 x IPN
· AC variable speed drives and servo
motor drives
Thermal drift of IO
0°C .. + 70°C
- 25°C .. + 85°C
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies
(UPS)
· Switched Mode Power Supplies
(SMPS)
tra
tr
Reaction time @ 10 % of IP max
< 500
< 1
> 200
DC .. 100
ns
µs
A/µs
kHz
Response time 3) 4) @ 90 % of IP max
di/dt di/dt accurately followed 4)
f
Frequency bandwidth 4) (- 1 dB)
General data
· Power supplies for welding
applications.
TA
TS
RS
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance @
- 25 .. + 85
- 40 .. + 90
32
33.5
40
°C
°C
W
W
g
TA = 70°C
TA = 85°C
m
Mass
Standards
5)
EN 50178
1)
Notes : Measuring range limited to ± 180 A max
2)
The result of the coercive field of the magnetic circuit
With a di/dt of 100 A/µs
The primary conductor is best filling the through-hole and/or the return
of the primary conductor is above the top of the transducer
A list of corresponding tests is available
3)
4)
5)
980716/5