5秒后页面跳转
ECL055-400E PDF预览

ECL055-400E

更新时间: 2024-11-15 06:49:23
品牌 Logo 应用领域
库柏 - COOPER 电路保护
页数 文件大小 规格书
7页 423K
描述
ELECTRIC FUSE, 400A, 5500VAC, 63000A (IR), INLINE/HOLDER

ECL055-400E 数据手册

 浏览型号ECL055-400E的Datasheet PDF文件第2页浏览型号ECL055-400E的Datasheet PDF文件第3页浏览型号ECL055-400E的Datasheet PDF文件第4页浏览型号ECL055-400E的Datasheet PDF文件第5页浏览型号ECL055-400E的Datasheet PDF文件第6页浏览型号ECL055-400E的Datasheet PDF文件第7页 
®
Bussmann  
E-Rated Medium Voltage Fuses: BoElBtI-0In55&& CECLL-01545  
For Transformer and Feeder Protection  
5.5 kV  
CATALOG SYMBOL: ECL055 & EBI055  
E-RATED MEDIUM VOLTAGE FUSES:  
Meets E requirements per ANSI C37.46  
Meets General Purpose requirements per ANSI C37.40  
FOR TRANSFORMER AND FEEDER PROTECTION  
VOLTAGE RATING: 5.5 KV  
INTERRUPTING RATING: 63KA Maximum Sym.  
CURRENT LIMITING  
CONSTRUCTION:  
• Silver element in a double concentric helical configuration  
Electrical Characteristics  
Bussmann  
Ampere  
IR  
# of  
• Silica filler  
Number  
Rating  
Voltage  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
5.5kV  
Max Sym.  
Barrels  
Figure #  
Style  
• Silver plated copper terminals and endcaps  
• Filament wound, glass epoxy fuse tube  
FEATURES:  
General Purpose Fuses. Bussmanns medium voltage fuses  
provide general purpose protection and are capable of interrupt-  
ing fault currents up to 63,000A RMS sym.  
Clip-lock and bolt-in style available in double and triple  
barrel fuse designs.  
Indoor and Outdoor Usage. The filament wound, glass epoxy  
fuse tube provides UV and moisture protection for the fuse. This  
makes Bussmanns medium voltage fuses suitable for both  
indoor and outdoor applications.  
Open Fuse Indication. Indicator travel distance is 16mm.  
Operating Frequency: 50/60 Hz  
ECL055-10E  
ECL055-15E  
ECL055-20E  
ECL055-25E  
ECL055-30E  
ECL055-40E  
ECL055-50E  
ECL055-65E  
ECL055-80E  
ECL055-100E  
ECL055-125E  
ECL055-150E  
ECL055-200E  
ECL055-250E  
ECL055-300E  
ECL055-400E  
ECL055-450E  
ECL055-500E  
ECL055-600E  
EBI055-750E  
EBI055-900E  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
125E  
150E  
200E  
250E  
300E  
400E  
450E  
500E  
600E  
750E  
900E  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
63kA  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
3
3
1
1
1
1
1
1
1
1
1
1
1
1
2
2
3
3
3
3
3
4
4
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Clip-Lock  
Bolt-In  
Dimensional Data:  
see pages 2-3.  
Bolt-In  
Performance Curves. see pages 4-7.  
Part Number Construction  
Catalog Symbol  
Voltage Rating  
055  
Ampere Rating  
Example  
ECL  
500E  
Current-limiting medium voltage fuses are classified  
into three categories:  
055 = 5.5 kV  
Catalog Number Cross Reference  
Full Range - defined by ANSI as “a fuse capable of interrupting  
all currents from the maximum rated interrupting current down  
to the minimum continuous current that causes melting of the  
fusible element(s), when the fuse is applied at the maximum  
ambient temperature specified by the manufacturer. It is able  
to interrupt any normal 60 cycle current that will melt its element.  
Ferraz-Shawmut  
New Catalog #  
Ferraz-Shawmut  
Bussmann  
Old Catalog #  
225-007-937  
225-007-938  
225-007-939  
225-007-940  
225-007-941  
225-007-942  
225-007-943  
225-007-944  
225-007-945  
225-007-946  
225-007-947  
225-007-948  
225-007-949  
225-007-950  
225-007-951  
225-007-952  
225-007-953  
225-007-954  
225-007-955  
A055X750E-4  
A055X900E-4  
ECL055-10E  
ECL055-15E  
ECL055-20E  
ECL055-25E  
ECL055-30E  
ECL055-40E  
ECL055-50E  
ECL055-65E  
ECL055-80E  
ECL055-100E  
ECL055-125E  
ECL055-150E  
ECL055-200E  
ECL055-250E  
ECL055-300E  
ECL055-400E  
ECL055-450E  
ECL055-500E  
ECL055-600E  
EBI055-750E  
EBI055-900E  
A055C1DORO-10E  
A055C1DORO-15E  
A055C1DORO-20E  
A055C1DORO-25E  
A055C1DORO-30E  
A055C1DORO-40E  
A055C1DORO-50E  
A055C1DORO-65E  
A055C1DORO-80E  
A055C1DORO-100E  
A055C1DORO-125E  
A055C1DORO-150E  
A055C1DORO-200E  
A055C1DORO-250E  
A055C1DORO-300E  
A055C1DORO-400E  
A055C2DORO-450E  
A055C2DORO-500E  
A055C2DORO-600E  
AO55B3DORO-750E  
AO55B3DORO-900E  
General Purpose - defined by ANSI C37.40 as “a fuse capable  
of interrupting all currents from the maximum rated interrupting  
current down to the current that causes melting of the fusible  
element in one hour. Not all currents fall within this range. It is  
possible to receive an overcurrent lower than the value given by  
the one hour criterion.  
Back-up - defined by ANSI C37.40 as “a fuse capable of inter-  
rupting all currents from the maximum rated interrupting current  
down to the rated minimum interrupting current.” The minimum  
rated interrupting current is the lowest current that the fuse will  
be able to clear properly. This creates a need to place a low  
current interrupting device in series with the back-up rated fuse.  
Form No. ECL055  
Page 1 of 7  
Data Sheet: 9002  
SB01488  
3-03-04  

与ECL055-400E相关器件

型号 品牌 获取价格 描述 数据表
ECL055-500E ETC

获取价格

Fuse
ECL055-50E COOPER

获取价格

Electric Fuse, 50A, 5500VAC, 63000A (IR), Inline/holder
ECL055-600E ETC

获取价格

Fuse
ECL055-750E ETC

获取价格

Fuse
ECL055-900E ETC

获取价格

Fuse
ECL05US03 OMRON

获取价格

530 Watts ECL Series
ECL05US03 XPPOWER

获取价格

530 Watts ECL Series
ECL05US05 OMRON

获取价格

530 Watts ECL Series
ECL05US05 XPPOWER

获取价格

530 Watts ECL Series
ECL05US05-E XPPOWER

获取价格

Ultra Compact Size