DRP BN1PH Series
6 0 - 4 8 0 W AT T S A C / D C D I N R A I L
FEATURES
•
•
•
•
•
•
•
•
•
•
•
24VDC 60W - 480W
1Ph AC/DC Power Supply
DIN Rail Mountable
Power will not de-rate for the entire input voltage range
Power Boost of 150% for 3 seconds
Conformal coating on PCBAs
To protect against common dust and chemical pollutants
Operating Temp -25C to 80C
MTBF DRP60W & 120W > 800 000hrs
MTBF DRP240W & 480W > 500 000hrs
Overvoltage / Overcurrent / Over Temperature / Protection
SPECIFICATIONS
OUTPUT
ENVIRONMENTAL
Output Voltage
Output Voltage Range
Output Current
Indicator
24Vdc, 48Vdc
Operating Temperature -25°C to +80°C
Storage Temperature -25°C to +85°C
24V - 28Vdc, 48V-56Vdc
See Selection Table
Power De-rating
Operating Humidity
Operating Altitude
MECHANICAL
> 50°C (2.5% / °C)
< 95% RH (Non-Condensing)
2,500m
Green LED (DC OK)
Output Power
Line Regulation
Load Regulation
PARD (20MHz)
Hold-up Time
INPUT
60W - 480W, See Selection Table
< 0.5% typ. (@ 85-264Vac input, 100% load)
< 1% typ. (@ 85-264Vac input, 0-100% load)
< 200mVpp
Case Cover
Aluminium
DRP60: 121 x 32 x 119.3mm, 0.33Kg
DRP120: 121 x 32 x 123.1mm, 0.72kg
DRP240: 121 x 85 x 124.1mm, 1.1kg
DRP480: 121 x 144 x 118.6mm, 1.37kg
> 20ms @ 115Vac & 230Vac
Dimensions / Weight
Input Voltage Range
Input Frequency
85–264VAC 120-375 VDC
47-63Hz
Indicator
Green LED (DC OK)
DRP60: <0.8A @ 230Vac
DRP120: < 1.2A @ 230Vac
DRP240: < 1.3A @ 230Vac
DRP480: <3A @ 230Vac
Input Terminal
Output Terminal
3 Pins (Rated 300V/30A)
4 Pins (Rated 300V/30A)
Input Current
DRP60: AWG 22-12
DRP120: AWG 20-12
DRP240: AWG 16-14
DRP480, AWG 18-10
Efficiency at 100% Load
Leakage Current
> 91.0% @ 115VAC >93.0% @ 230VAC
< 1mA @ 240VAC
Input Wire
PROTECTIONS
DRP60: AWG 22-12
DRP120: AWG 20-12
DRP240: AWG 16-14
DRP480: AWG 18-10
32V, +/-10% SELV Ouput, Hiccup Mode, Non-
Latching (Auto-Recovery)
Overvoltage
Output Wire
> 150% of rated load current, Hiccup Mode, Non-
Latching (Auto-Recovery)
Overload/Overcurrent
Over Temperature
Short Circuit
Mounting Rail
IEC AC Input
Drip Hood Cover
STANDARDS
C-Tick
TS35 DIN Rail in accordance with EN60715
See PBB1P Series for IEC Input option
< 80C Surrounding Air Temperature @ 100%
load, Non-Latching (Auto Recovery)
See PBB1P Series for Drip Hood Cover option
Hiccup Mode, Non-Latching (Auto-Recovery)
when the fault is removed)
Degree of Protection
IP20
AS/NZS CISPR11 Group 1 Class A.
Protection against shock
Class 1 with PE (Primary Earth) connection
Electronic Equipment EN50718 / IEC62103 in Power Installatioins
SIQ to EN60950-1, UL/cUL recognized to
Input to Output: 4.0KVAC
Input to Ground: 1.5KVAC
Output to Ground: 1.5KVAC
Galvanic Isolation
RELIABILITY
Electrical Safety
UL60950-1, CSA C22.2 No. 60950-1, CB scheme
to IEC60950-1
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-
01, CSA to CSA C22.2 No. 107.1-01 (File No.
181564)
DRP60W & DRP20W: 800,000 hrs as per Telcordia
SR-332 I/P: 115Vac, O/P: 100% load, Ta 25C
DRP240W & DRP480W: 500,000 hrs as per
Telcordia SR-332 I/P: 115Vac, O/P: 100% load, Ta
25C
Industrial Control
MTBF
In conformance with EMC Directive 2004/108/EC
and Low Voltage Directive 2006/95/EC
CE
Materials & Parts
RoHS Directive 2011/65/EU Compliant
Expected Life Time
10 years (230Vac 50% load @ 40C)
Doc. No. DRP BN1PH Series Rev.A 16-9-15
1