240W Single Output Industrial DIN RAIL Power Supply
DRP-240 series
Features :
Universal AC input / Full range
Built in active PFC function
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 100KHz
3 years warranty
SPECIFICATION
MODEL
DRP-240-24
DRP-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
10A
5A
0 ~ 10A
240W
0 ~ 5A
240W
150mVp-p
48 ~ 53V
1.0%
RIPPLE & NOISE (max.) Note.2 80mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 1.0%
OUTPUT
24 ~ 28V
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
0.5%
0.5%
1.0%
1.0%
800ms, 40ms/230VAC
800ms, 40ms/115VAC at full load
24ms/230VAC
Note.5 85 ~ 264VAC
47 ~ 63Hz
24ms/115VAC at full load
120 ~ 370VDC
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
0.96/230VAC
84%
0.99/115VAC at full load
1.4A/230VAC
INPUT
85%
2.8A/115VAC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
COLD START 27A/115VAC
<3.5mA / 240VAC
45A/230VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
54 ~ 60V
30 ~ 36V
PROTECTION OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
100
5
(TSW1)detect on heat sink of power transistor
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-10 ~ +70 (Refer to output load derating curve)
WORKING TEMP.
WORKING HUMIDITY
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
0.03%/ (0 ~ 50
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
SAFETY &
ISOLATION RESISTANCE
EMC
(Note 4)
Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
105.5Khrs min. MIL-HDBK-217F (25
125.5*125.2*100mm (W*H*D)
)
OTHERS
NOTE
DIMENSION
PACKING
1.2Kg; 12pcs/15.5Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:DRP-240-SPEC 2008-04-07