AC-DC Power Supplies
CMP250 Series
250/500 Watts Peak
• 250 W Convection-cooled Rating
• 500 W Peak Power
• IT & Medical Safety (BF) Approvals
• U Channel 4”x 7.5” Package
• 80 VAC to 300 VAC Input
• 5 V/1.5A Standby & 12 V/0.6 A Auxiliary
• AC OK Signal, Inhibit
• Current Share
• 3 Year Warranty
Dimensions:
The universal AC input CMP250 provides up to 500 W peak power and 250 W convection-cooled in a
7.5” x 4” package, over the temperature range -40 °C to +50 °C with derating to +70 °C. Approved for
IT and Medical (BF) applications and with a feature set including constant current overload
characteristics, a 5 V/1.5 A standby output, 12 V/0.6 A auxiliary, AC OK signal, inhibit, current share the
CMP250 is ideal for motors and other electromechanical loads, without the need for fan cooling, in both
industrial and medical applications.
CMP250:
7.50 x 4.00 x 1.57” (190.5 x 101.6 x 39.9 mm)
CMP250-C:
7.89 x 4.12 x 1.92” (200.5 x 104.6 x 48.8 mm)
Models & Ratings
Output Current V1
Output Power
Standby Supply
V2
Aux. Supply
V3
Output Voltage V1
Model Number(1)
Convection
Peak
20.8 A
13.8 A
10.4 A
Convection
250 W
Peak(2)
500 W
500 W
500 W
24 V
36 V
48 V
10.4 A
6.9 A
5.2 A
5.0 V / 1.5 A
5.0 V / 1.5 A
5.0 V / 1.5 A
12.0 V / 0.6 A
12.0 V / 0.6 A
12.0 V / 0.6 A
CMP250PS24
CMP250PS36
CMP250PS48
250 W
250 W
Notes
1. Add suffix '-C' for covered version, e.g. CMP250PS24-C (20% derating applies)
2. Peak current/power available for up to 1 minute. Average power must not exceed 225 W, other peak and average load conditions can be accommodated limited by
the thermal considerations and average power rating. Peak power and average power derate below 90 VAC.
Summary
Characteristic
Minimum
Typical
Maximum
264
Units
Notes & Conditions
80
115/230
Derate output power <90 VAC, see fig.1
Input Range
VAC
300
0.5 seconds max
No Load Input Power
Input Frequency
1.3
W
All models, when optional inhibit activated
47
50/60
63
Hz
EN61000-3-2 class A compliant
EN61000-3-2 class C for loads ≥50%
115/230 VAC. 500 W
Power Factor
>0.95
Input Current - Full Load
Inrush Current
5.2/2.6
30
A
A
40
250
80
Cold start 25 °C, 230 VAC
Earth Leakage Current
Patient Leakage Current
Efficiency
100/200
55
µA
µA
%
Typ. 115/230 VAC 50 Hz, Max 264 VAC 60 Hz
89
230 VAC, 250 W
See derating curve, fig.8 and Thermal Considerations on
page 8
Operating Temperature
EMC
-40
+70
°C
EN55032/11 Class B Conducted & Radiated, EN61000-3-2, EN61000-3-3
EN62368-1, UL62368-1, CSA C22.2 No. 62368-1, IEC62368-1, IEC60950-1 Ed 2, IEC60601-1 Ed 3 Including Risk Management,
ANSI/AAMI ES60601-1:2005 & CSA C22.2, No.60601-1:14
Safety Approvals