Bus s m a nn
Dis c onne c t Switc h
Fus ible , 60-100A, 6 0 0 V
BDF6 0 a nd
BDF1 0 0
BDF6 0 J 6
BDF1 0 0 J T6
Components:
Handles
Ca ta log Sym bols *: BDF60J6, BDF100JT6
Am pe re Ra ting: 60 to 100 Amperes
Volta ge Ra ting: 600 Volts
Grip
NEMA
Length
Padlock- Defeat- Catalog
Style
Type
Color (Inches) Marking
able
able
Number
Age nc y Approva ls :
60-100A ( 0.24∑ x 0.24∑)
▫
UL Listed, Guide WPZX, File E155129
CSA Certified, File 58077M9
IEC 947-1
Pistol
Pistol 1, 3R, 12
Pistol 4, 4X
1, 12
Blk
Blk
Blk
3.15
2.36
2.36
Off/On
Off/On
Off/On
Yes
Yes
Yes
Yes
Yes
No
BDH20
BDH50
BDH57
Ge ne ra l Inform a tion:
Bussmann fused disconnect switches are UL 98/CSA 22.2 No. 4
devices. This makes them suitable for use on service equipment,
panel boards, switchboards, industrial control equipment, motor
control centers, etc.
Terminal Lug Kits - Kit Includes 6 Lugs
Amp Rating
Wire Size
Wire Type
Kit Catalog Number
100
200
400
#14 - 2/0
#6 - 300 kcmil
#2 - 600 kcmil
(2) #2 - 600 kcmil
Cu/Al
Cu/Al
Cu/Al
Cu/Al
BDTL24
BDTL25
BDTL26
BDTL27
*Catalog symbol is for switch only. Handles and shafts are ordered separately.
600 & 800
Shafts
Fuse
Type
J
Maximum Horsepower Rating
Mounting Depth**
Shaft Length
Catalog Number
200V
15
208V
15
240V
15
480V
30
600V
40
60 - 100 Amps ( 0.24∑ x 0.24∑)
▫
BDF60J6
5.50 - 8.50
8.00 - 11.00
11.00 - 14.00
13.75 - 16.75
16.54 - 19.69
5.90
8.26
11.41
14.17
16.93
BDS150
BDS210
BDS290
BDS360
BDS430
BDF100JT6
J†
25
25
30
40
50
†Class J fuses are standard. If 600V Class T fuses are desired, us BDTA1 adapters.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
**Mounting depth is measured from outside panel door to mounting plate of disconnect. Shaft can
be cut to desired length.
Accessories:
Fuse Covers and Terminal Shrouds (line-side)
Switch Type
Fuse Covers
Catalog
Number
Terminal Shrouds
Catalog
Amp
Rating
Fuse
Type
Voltage
Number
60
100
J
600V
600V
BDFC60J
BDFC100
Not Required
BDTSF1
J or T
Auxiliary Contacts - F60 through F100
Switch
Aux. Contact
1 N.O. & 1 N.C.
2 N.O. & 2 N.C.
Amp Rating Amp Rating
Voltage Catalog Number Catalog Number
60
100
6
6
250
250
BDAUX7
BDAUX7
BDAUX8
BDAUX8
Form No. BDF
12-17-98
Page 1 of 2
BIF Doc #1121
SB98107