AZ2800
30 AMP MINIATURE
POWER RELAY
FEATURES
• DPST-NO and DPDT configuration
• Meets 8 mm creepage, 4 kV dielectric
• Epoxy sealed versions available
• UL Class F (155°C) standard
• UL, CUR file E44211
• VDE certificate 40023442
CONTACTS
Arrangement DPST (2 Form A)
DPDT (2 Form C)
GENERAL DATA
Ratings
Resistive load:
Life Expectancy
Mechanical
Electrical
Minimum operations
5 x 107
1 x 105 at 30 A 277 VAC Res. (N.O.)
Max. switched power: 560 W or 8310 VA
Max. switched current: 30 A (N.O), 3 A (N.C.)
Max. switched voltage: 30 VDC* or 600 VAC
Operate Time
15 ms typical
25 ms maximum with bounce
*Note: If switching voltage is greater than 30VDC,
special precautions must be taken. Please contact
the factory.
Release Time
10 ms typical
25 ms maximum with bounce
(with no coil suppression)
Rated Load
UL
Normally open contacts (N.O.)
30 A at 277 VAC General Use, 100k cycles [1][2]
10 A at 600 VAC, General Use, 6k cycles [1]
1 HP at 120 VAC, 100k cycles [1][2]
Dielectric Strength
(at sea level for 1 min.) 4000 Vrms contact to coil
1500 Vrms contact to contact
2000 Vrms between contact sets
2.5 HP at 240 VAC, 100k cycles [1][2]
8 FLA / 26 LRA at 277, 480, 600 VAC, 30k cycles [1]
Insulation Resistance 109 ohms minimum at 500 VDC
Dropout
DC:Greater than 10%of nominal coil voltage
AC: Greater than 20%of nominal coil voltage
Normally open contacts (N.O.), DC Coils only
25.3 FLA / 110 LRA at 240 VAC, 30k cycles [1][2]
Ambient Temperature At nominal coil voltage
Normally closed contacts (N.C.)
Operating
DC: -40°C (-40°F) to 85°C (185°F)
3 A at 277 VAC, General Use, 100k cycles [1][2]
2 A at 480 VAC, General Use, 6k cycles [1]
1 A at 600 VAC, General Use, 6k cycles [1]
3 FLA / 3 LRA at 240 VAC, 30k cycles [1]
2 FLA / 2 LRA at 277, 480 VAC, 30k cycles [1]
1 FLA / 1 LRA at 600 VAC, 30k cycles [1]
AC: -40°C (-40°F) to 65°C (149°F)
-40°C (-40°F) to 105°C (221°F)
Storage
Vibration
0.062" (1.5 mm) DA at 10–55 Hz
Shock
Operational, 10 g for 11 ms 1/2 sine pulse
(no contact opening > 100usec)
Non-destructive, 100 g for 11 ms 1/2 sine pulse
VDE
Normally open contacts (N.O.)
20 A at 250 VAC, Resistive, 50k cycles [2]
Enclosure
Terminals
P.B.T. polyester
Normally closed contacts (N.C.)
3 A at 250 VAC, Resistive, 50k cycles [2]
Quick connect tabs
Note: Allow suitable slack on leads when wiring,
and do not subject the terminals to excessive
force.
Material Silver cadmium [1], silver tin oxide [2]
Resistance <50 milliohms initially
Max. Solvent Temp.
80°C (176°F)
(6 V, 1 A voltage drop method)
Max. Immersion Time 30 seconds
COIL
Weight
86 grams
Power
At Pickup Voltage
(typical)
Packing unit in pcs
20 per plastic tray / 100 per carton box
925 mW, DC coil
2.6 VA, AC coil
Max. Continuous
Dissipation
5.0 W at 20°C (68°F) ambient, DC coil
7.0 VA at 20°C (68°F) ambient, AC coil
NOTES
1. All values at 20°C (68°F).
Temperature Rise
48°C (86°F) at nominal coil voltage, DC coil
68° C (122°F) at nominal coil voltage, AC coil
2. Relay may pull in with less than “Must Operate” value.
3. Specifications subject to change without notice.
Temperature
Max. 155°C (311°F)
3/12/15