Thermal-magnetic (TM and AS-line)
AS168X Add-on modules
https://www.schurter.com /PG20
Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic
Auxiliary contact
Signal contact
Relay trip module
See below:
Approvals and Compliances
Description
Applications
- DIN-Rail Mounting
- Auxiliary contact module
- Industrial appliances
References
Last order possibility: 31.08.2018
Last delivery date: 30.09.2018
Each auxiliary contact module contains one contact, either normally
open or normally closed
- Signal contact module
Signal contact modules are linked internally with the protected poles
but not linked at the handles. Contacts are actuated by a fault condi-
tion at the protected poles, not by manual operation of the CBE
- Relay trip module
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
The relay trip module can be used for remote tripping of the adjacent
poles by applying a voltage to the module's terminal
Technical Data
Ratings
AC 277 V / 6 A (50/60 Hz)
DC 125 V / 1 A
Overload
AC: min. 10trips
@ 10 x Ir, p.f. = 0.3
DC: min. 50trips
@ 1.1 x Ir, L/R = 0.3 s
-20°C to 60°C
DC 50 V / 6 A
IEC: Inc, PC1, AC 277 V: 1 kA
Conditional short circuit ca-
pacity
Dielectric Strength
Ambient temperature
Vibration Resistance
0.75 mm @ 10 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
30 G / 18ms
acc. to IEC 60068-2-27, test Ea
from front side IP 20 acc. to IEC 60529
22 - 49g
50Hz: > 2kV
Impulse 1.2/50 μs
> 5 MΩ
mechanical: 50000switching cycles
IEC 60947-5-1
AC : 10 x Ir , p.f. = 0.3 :
DC : 1 x Ir , L/R = 0.3 s :
6050switching cycles
Insulation Resistance
Endurance typical
Shock Resistance
Degree of Protection
Weight
AC : 26 A / 2.6 A , p.f. = 0.35 :
DC : 1.1 A / 1.1 A , L/R = 0.3 s :
6000switching cycles
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: AS168X
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
VDE Certificate Number: 40021845
UL Approvals
UL Approvals
UL
UL
UL File Number: E216629 / E71572
UL File Number: E216629 / E71572
1