411 SERIES
FIRELITE ALARMS
DIGITAL ALARM COMMUNICATOR
TRANSMITTER
DESCRIPTION
The Firelite Alarms 411 Series Digital Alarm
Communicator Transmitters are compact, multifaceted and
designed for a variety of fire applications. The Model 411
provides three (3) monitoring channels (inputs) while the
Model 411UD provides four (4) monitoring channels.
The 411 Series are a cost-effective solution for applications
requiring an existing (or new) fire alarm control to transmit
system status to an off-site monitoring facility for Central or
Remote Station(DACT) compliance perNFPAStandard 72.
The transmitters provide fifteen (15) selectable
transmission formats, including Ademco Contact ID, for
compatibility with virtually all Digital Alarm Communicator
Receivers (DACR).
In addition to vital system status of the main control panel,
the 411 Series is capable of transmitting DACT Trouble,
Telephone line 1 and 2 Voltage Faults, Primary or Secondary
Central Station Communication Faults, System Off-normal,
24-hour Normal Test and 24-hour Abnormal Test.
The transmitters are new long-distance Carrier Access
Code (CAC) compliant, accepting up to 20-digit Central
Station telephone numbers. They also have the industry-first
UL Recognized “dialer runaway” prevention feature.
Programming may be accomplished on-site with a Model
PRO-411 hand-held programmer. The 411UD can also be
programmed remotely with the optional PK-411UD
Windows® based remote upload/download software
package. The software also permits system interrogation and
revision from a remote site.
The transmitter is housed in a compact cabinet measuring
6.75" (17.1 cm) wide, 4.4" (11.2 cm) high, and 1.05" (2.7 cm)
deep, allowing it to be mounted inside or adjacent to the fire
alarm control cabinet.
Two modular phone connections are accessible with the
cover in place and provide connections for two separate
telephone lines using standard RJ31X or RJ38X jacks. Both
lines are constantly supervised for proper voltage and
current. Should one phone line go into fault and the other
remain operational, a report is sent to the central or remote
station.
FEATURES
· Field Programmable using PRO-411
Hand-held Programmer
· Programmable Transmittal Codes
· 411UD Programmable from Remote
Site with PK-411UD Software
(Optional)
· Individually Programmable Dry
Contact Inputs for Alarm, Trouble and
Supervisory Signals
· Compact Housing for Convenient
Mounting
· Surface Mount Technology
· Programmable AC Loss Reporting
ORDERING INFORMATION
Delay
Part No.
Model
Description
Diagnostic LEDs are as follows:
· Communication Fail (Visible with cover in place)
190-90010 411
Three-Channel, Dual-line
DACT
· DACT Trouble (Visible with cover in place)
· Channel Active (Visible with cover in place)
· Primary Phone Line active (411UD)
· Secondary Phone Line Active (411UD)
· Modem Active (411UD)
190-90011 411UD
Four-Channel DACT with
Form “C” programmable
Relay, Silence Switch
and remote upload/
/download capability.
190-90012 PRO-411
Hand-held programmer
for 411 and 411UD
200-90000 PK-411UD Software kit for 411UD
600-90000 MCBL-7 DACT phone cord, 7 ft.
(2 req.)
Windows® is a Registered Trademark of the Microsoft Corporation.
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by
Gamewell-FCI for their use. Specifications subject to change without notice. 2006 All Rights Reserved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
9020-0460 Rev. B 1 of 1
An ISO 9001 Certified Company