MODEL: 18KDYH2  
Rack-mounted DCS Signal Conditioners 18K-RACK  
[2] OPTIONS (multiple selections)  
Opencircuit detection  
blank: none  
CURRENT LOOP SUPPLY  
(applicable to HART signal, opencircuit detection selectable)  
Functions & Features  
/B: Opencircuit detector (Only for HART signal)  
Connector output polarity reversal  
blank: none  
• Powers a 4 – 20 mA DC current loop  
• Isolates and relays HART signals  
• Shortcircuit protection  
/RE: Connector output polarity reversal (Only for HART signal)  
• Opencircuit detection selectable  
• Module can be retracted without removing wiring for an  
insulation test  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
Typical Applications  
Connection  
• 2-wire HART transmitters  
Input: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
Output 1: Connector  
Output 2: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
Power input: Supplied from connector  
Screw terminal: Nickel-plated steel  
Isolation: Input to output 1 to output 2 to power  
Overrange output: Approx. -10 to +110 %  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
Open-circuit detection: This function enables the input  
device to detect open circuit of output circuit isolated from  
the input circuit.  
MODEL: 18KDYH2–A[1]–R[2]  
ORDERING INFORMATION  
• Code number: 18KDYH2-A[1]-R[2]  
Specify a code from below for each of [1] and [2].  
(e.g. 18KDYH2-A6A-R/B/RE)  
Input current 0 mA when the output loop is open.  
Photo MOSFET Relay ON Resistance; 3 Ω max.  
SUPPLY OUTPUT  
(across the terminals 1 – 2)  
Output voltage: 24 – 28 V DC with no load  
18 V DC at 20 mA  
INPUT  
Current  
A: 4 - 20 mA DC (Input resistance approx. 250Ω)  
Current rating: ≤ 22 mA DC  
• Shortcircuit Protection  
[1] OUTPUT 1 / OUTPUT 2  
Current limited: 30 mA max.  
Protected time duration: No limit  
6A: 1 – 5 V DC (Load resistance 2000 Ω min.)  
/ 4 – 20 mA DC (Applicable to HART signal, load resistance 600 Ω max.)*  
A6: 4 – 20 mA DC (Applicable to HART signal, load resistance 600 Ω max.)*  
/ 1 – 5 V DC (Load resistance 2000 Ω min.)  
INPUT SPECIFICATIONS  
DC Current: Input resistor incorporated  
Input current: ≥ 0 mA  
AA: 4 – 20 mA DC (Applicable to HART signal, load resistance 600 Ω max.)*  
/ 4 – 20 mA DC (Load resistance 500 Ω max.)  
* 250 Ω ±10% for HART communication  
OUTPUT SPECIFICATIONS  
The output goes below 0 % when the input is open.  
Polarity of connector output is reversed with option code  
/RE (with connector output polarity reversal).  
POWER INPUT  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
18KDYH2 SPECIFICATIONS  
ES-0430 Rev.3 Page 1/5  
http://www.m-system.co.jp/  

与18KDYH2-AA6-R/RE相关器件

型号 品牌 获取价格 描述 数据表
18KDYH2-AAA-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDYH2-AAA-R/B MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDYH2-AAA-R/RE MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KJDL MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KJDL-A066-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KJDL-A066-R/S MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KJDL-A166-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KJDL-A166-R/S MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KJDL-A266-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KJDL-A266-R/S MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK