MODEL: 18KJPA
Rack-mounted DCS Signal Conditioners 18K-RACK
OUTPUT 2
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
FREQUENCY TRANSMITTER
(field-programmable)
Functions & Features
POWER INPUT
• Converting the output from a pulse-type transducer into
two standard process signals
DC Power
R: 24 V DC
• Microprocessor based
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Field-programmable frequency range
• Linearization available for flow compensation
• Averaging non-uniform pulses
• Excitation
[2] OPTIONS
Power Switch
blank: None
• Loop testing via hand-held programmer PU-2x
• Module can be retracted without removing wiring for an
insulation test
/S: With power switch
RELATED PRODUCTS
• Power switch optional
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals on the front and connector on the rear; terminal
cover provided
MODEL: 18KJPA–[1]66–R[2]
ORDERING INFORMATION
• Code number: 18KJPA-[1]66-R[2]
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
and connector
Specify a code from below for each [1] and [2].
(e.g. 18KJPA-266-R/S)
Output 1: Connector
• Frequency range (e.g. 0 – 152.3 Hz)
• Linearization data (max. 16 points)
Output 2: M3.5 screw terminals (torque 0.8 N·m)
and connector
Use Ordering Information Sheet (No. ESU-1673) to specify
linearization data when the I/O signals are non-linear.
Note: Consult factory on applications with a sensor handling
periodically (& quickly) changing frequency (e.g. oval
flowmeter).
Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Input to output 1 to output 2 to power
Overrange output: -10 – +120 % at 1 – 5 V
(0 – 120 % when 0 % input equals to 0 Hz.)
Linearization: 16 points max. represented as percentage of
full-scale
[1] INPUT
1: Open collector (Excitation: 12 V @ 30 mA)
2: Voltage pulse (Excitation: 12 V @ 30 mA)
3: Mechanical contact (Excitation: 12 V @ 30 mA)
Adjustments: Programming Unit (model: PU-2x); input
range, low-end cutout, zero and span, simulating output,
averaging nonuniform pulses, linearization data, etc.
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON.)
OUTPUT 1
Low-end cutout: 0 – 100 % adjustable (factory set to 0 %);
hysteresis fixed to 1 %
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
18KJPA SPECIFICATIONS
ES-0473 Rev.5 Page 1/4
http://www.m-system.co.jp/